54
Setting outdoor unit option switch and key function
English
Instal
lation Pr
oc
edur
e
Optional item
Input unit
SEG1
SEG2
SEG3
SEG4
Function of the option
Remarks
Emergency operation
for compressor
malfunction
Individual
0
0
0
0
Disabled (Factory default)
E560 will occur when all the
compressors are set as malfunction
state.
0
1
Set compressor 1 as malfunction
state
0
2
Set compressor 2 as malfunction
state
Capacity correcton
for cooling
Main
0
1
0
0
7-9
Targeted evaporation temperature
[°C].
(When low temperature value is set,
discharged air temperature of the
indoor unit will decrease)
0
1
5-7 (Factory default)
0
2
9-11
0
3
10-12
0
4
11-13
0
5
12-14
0
6
13-15
Capacity correction
for heating
Main
0
2
0
0
3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
0
1
2.5
0
2
2.6
0
3
2.7
0
4
2.8
0
5
2.9
0
6
3.1
0
7
3.2
0
8
3.3
Current restriction
rate
Individual
0
3
0
0
100% (Factory default)
When restriction option is set,
cooling and heating performance
may decrease.
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the product is
being installed in humid area such
as near river or lake
Fan speed correction
for outdoor unit
Individual
0
6
0
0
Factory default
0
1
Increase fan speed
Increase the outdoor unit's fan speed
to maximum value
Summary of Contents for AM AXV Series
Page 68: ......