3-22
3-23
Disassembly and Reassembly
3-22
No
Parts
Procedure
Remark
3)
Remove 1 screw from the Cover Pipe fastening the
In/Out Pipe to remove it (use +SCREWDRIVER).
4)
Remove the heat exchanger from the fan coil unit
cabinet.
When turning on the cold/hot water after
replacing the heat exchanger, make sure
to open the air release valve to sufficiently
remove air from inside the coil and pipe by
collecting the water using the tube before
closing the valve. Failure to do so may
result in decreased performance and noise
generation.