Check and test operation
1. Supply power to the air conditioner.
2. Turn on the air conditioner.
3. While pressing and holding the
Set/Cancel
button on the remote controller, press the
Powe
r button for 3 seconds to
display the temperature of indoor heat exchanger.
- Write down the displayed temperature.
4. Press the
Turbo
button on the remote controller to operate in turbo mode for 10 minutes.
5. Check if the indoor unit is operating normally.
- Standard condition to judge normal operation. (Indoor/outdoor unit over 21°C, operate in Cool mode for over 10
minute)
6. While pressing and holding the
Set/Cancel
button on the remote controller, press the
Power
button for 3 seconds to
display the temperature of indoor heat exchanger.
- If the displayed temperature differs over 10°C from the temperature written down previously, it is operating normally.
7. When checking above step 1~6 is done, tell the user how to use the air conditioner.
Pump down procedure (When removing the product)
1. Press the
Powe
r button on the indoor unit control panel for 5 seconds to enter the Pump down mode and operate
the compressor for over 5 minutes. Or, Press the
Set/Cancel, Mode
and
Temp -
button on the remote controller
simultaneously to enter the Pump down mode and operate the compressor for over 5 minutes.
2. Remove the
High/Low
pressure side valve cap.
3. Use the L wrench to completely close the valve on the high pressure side.
4. After 2 minutes, completely close the valve on the low pressure side.
5. Press the
Powe
r button on the indoor unit control panel for 5 seconds to deactivate the Pump down mode. Or, Press
the
Set/Cancel, Mode
and
Temp
- button on the remote controller simultaneously to deactivate the Pump down mode.
6. Disconnect the pipe.