38
Indoor/outdoor unit installation diagram
Maximum
allowable piping
elevation 10m
or less
6m or
less
Install S-trap for
every 6m
Maximum allowable
piping length 20m
or less
Outdoor unit
50cm
or more
30c
m o
r
mo
re
50cm or
more
Air guide
(Not provided by
manufacturer )
30cm or more
20cm or more
No
obs
tacl
e
1m
or m
ore
60cm
or m
ore
30cm or
more
Protection
vinyl
Outdoor
unit leg
Rubber leg
Spare space for piping
• One S-trap must be installed on the low pressure
pipe up to 6m of piping elevation. For piping
elevation that exceeds 6m, install S-trap every
6m.
CAUTION
Piping length for indoor/outdoor unit installation
f
f
Refer to illustration on the left for maximum allowable
piping length and elevation.
f
f
Since product performance and lifespan may decrease as
piping length becomes longer, try to minimize the piping
length but make sure it is over 5m.
f
f
Select the installation location where you can keep the
piping bending to maximum 10 spots.
f
f
Stated cooling performance is based on product with 5m
piping.
Installation space for floor type indoor unit
f
f
To minimize the waste of space due to installation, install the indoor unit as
shown in below figure.
-
Top view
❋
❋
After completing the installation, remove the protection vinyl.
(Be careful of static electricity).
❋
❋
After completing the installation, remove the protective
filament film on the product.
• Make sure that there are no obstacles (such as curtains etc.) blocking air
inlets of the indoor unit.
• Clear space on the right side of the indoor unit for possible filter
maintenance in the future.
CAUTION
When air guide needs to be installed to prevent the warm discharge air from
disturbing the pedestrian, refer to the illustration on the right side for installation.