22
Installation Procedure
English
Ins
tallation Pr
oc
edur
e
6
View mode: When the K4 switch is pressed, you can see information about our system state as below.
K4
short
push
Display contents
SEG1
SEG2
SEG3
SEG4
Unit
1
Order frequency
1
Hundreds digit
Tens digit
Units digit
Hz
2
Current frequency
2
Hundreds digit
Tens digit
Units digit
Hz
3
The number of connected
indoor units
3
Hundreds digit
Tens digit
Units digit
EA
4
Ambient temperature
sensor
4
+ / -
Tens digit
Units digit
°C
5
Compressor discharge
sensor
5
Hundreds digit
Tens digit
Units digit
°C
6
Eva-Mid sensor
6
+ / -
Tens digit
Units digit
°C
7
Condensor sensor
7
+ / -
Tens digit
Units digit
°C
8
Current
8
Tens digit
Units digit
The first place of
decimals
A
9
Outdoor fan RPM
9
Thousands digit
Hundreds digit
Tens digit
rpm
10
Target discharge
temperature
A
Hundreds digit
Tens digit
Units digit
°C
11
EEV
B
Hundreds digit
Tens digit
Units digit
step
12
The capacity sum of indoor
units
C
Tens digit
Unit digit
The first place of
decimals
kW
13
Protective control
D
0: Cooling
1: Heating
Protective control
0: No Protective
control
1: Freezing
2: Non-stop
defrosting
3: Over-load
4: Discharge
5: Total electric
current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14
IPM temperature
E
Hundreds digit
Tens digit
Units digit
-
15
The number of indoor units
F
-
-
-
-
Display contents
SEG1
SEG2
SEG3
SEG4
K4
long
push
-
Main micom version
Year (Dec)
Month (Hex)
Date (Tens digit)
Date (Units digit)
After short
push 1
Inverter micom version
Year (Hex)
Month (Hex)
Date (Tens digit)
Date (Units digit)
After short
push 2
E2P version
Year (Hex)
Month (Hex)
Date (Tens digit)
Date (Units digit)
• Long push K4 (Main micom ver.)
short push 1 more (Inv. micom ver.)
short push 1 more (E2P. ver.)
360_AC_Outdoor_AU_Eng_EN.indb 22
2016-09-20 오후 8:00:35