12
Installation Procedure
English
Ins
tallation Pr
oc
edur
e
• Connect the rated cables only.
• Connect using a driver which is able to apply the
rated torque to the screws.
• If the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal
may be damaged.
Tightening torque (kgf • cm)
M4
12.0 to 18.0
Communication : F1, F2
M5
20.0 to 30.0
1-phase AC power: 1(L), 2(N), L, N
• 1N · m = 10 kgf · cm
CAUTION
• When connecting cables, you can connect the cables
to the electrical part or connect them through the
holes below depending on the spot.
• Connect the communication cable between the
indoor and outdoor units through a conduit to protect
against external forces, and feed the conduit through
the wall together with refrigerant piping.
• Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such
as rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power
cable and communication cable.
• When the cables are connected through the hole,
remove the Plate bottom.
Outdoor-to-indoor power and communication
cables specifications
Indoor power supply
Power supply
Max/Min (V)
Indoor power cable
1
Φ
, 220-240V,
50 Hz
±10%
0.75 to 1.5 mm²,
3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
CAUTION
• When installing the indoor unit in a computer
room or a server room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
Nominal
dimensions
for cable
(mm²)
Nominal
dimensions
for screw
(mm)
B
D
d1
E
F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
Min.
(mm)
Max.
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
4/6
4
9.5
±0.2
5.6
+0.3
-0.2
3.4
±0.2
6
5
20
4.3
+0.2
0
0.9
8
15
9
28.5
8.4
+0.4
0
10
8
15
±0.2
7.1
+0.3
-0.2
4.5
±0.2
7.9
9
30
8.4
+0.4
0
1.15
16
8
16
±0.2
9
+0.3
-0.2
5.8
±0.2
9.5
13
33
8.4
+0.4
0
1.45
25
8
12
±0.3
11.5
+0.5
-0.2
7.7
±0.2
11
15
34
8.4
+0.4
0
1.7
8
16.5
13
8.4
35
8
16
±0.3
13.3
+0.5
-0.2
9.4
±0.2
12.5
13
38
8.4
+0.4
0
1.8
8
22
13
43
8.4
50
8
22
±0.3
13.5
+0.5
-0.2
11.4
±0.3
17.5
14
50
8.4
+ 0.4
0
1.8
70
8
24
±0.4
17.5
+0.5
-0.4
13.3
±0.4
18.5
20
51
8.4
+ 0.4
0
2.0
360_AC_Outdoor_AU_Eng_EN.indb 12
2016-09-20 오후 8:00:31