![Samsung AC NX S C Series Installation Manual Download Page 23](http://html.mh-extra.com/html/samsung/ac-nx-s-c-series/ac-nx-s-c-series_installation-manual_336654023.webp)
AA
23
English
ENGLISH
Performing leak tests
The designs and shape are subject to
change according to the model.
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before recreating the vacuum
and recirculating the R-410A, it’s responsable of installer to pressurize the
whole system with nitrogen (using a cylinder with pressure reducer) at a
pressure above 2 bar, less than 40 bar (gauge).
LEAK TEST WITH R-410A (after opening valves)
Before opening valves, discharge all the nitrogen into the system and create
vacuum. After opening valves check leaks using a leak detector for refrigerant
R-410A.
Once you have completed all the connections, check for possible leaks using
leak detector specifically designed for HFC refrigerants.
To check for gas leaks on the
Then, using a leak detector, check the
Outdoor unit
Valves on sections A and B.
A(Gas)
B(Liquid)
Summary of Contents for AC NX S C Series