![Samsung AC NX S C Series Installation Manual Download Page 18](http://html.mh-extra.com/html/samsung/ac-nx-s-c-series/ac-nx-s-c-series_installation-manual_336654018.webp)
AA
18
English
1. Prepare the following tools.
Tools
Crimping pliers
Connection sleeve
(mm)
Insulation tape
Contraction tube
(mm)
Spec
MH-14
20xØ6.5(HxOD)
Width 19mm
70xØ8.0(LxOD)
Shape
2.
As shown in the figure, peel off the shields from the rubber and wire of
the power cable.
- Peel off 20 mm of cable shields from the pre-installed tube.
CAUTION
• For information about the power cable specifications for indoor
and outdoor units, refer to the installation manual.
•
After peeling off cable wires from the pre-installed tube, insert
a contraction tube.
(Unit: mm)
120
60
20
20
20
180
Power cable
20
Pre-installed tube for the power cable
3. Insert both sides of core wire of the power cable into the connection
sleeve.
f
Method 1
Push the core wire into the sleeve from both sides.
Connection sleeve
f
Method 2
Twist the wire cores together and push it into the sleeve.
Connection sleeve
4.
Using a crimping tool, compress the two points and flip it over and compress another two points in the same
location.
- The compression dimension should be 8.0.
-
After compressing it, pull both sides of the wire to make sure it is firmly pressed.
Compression
dimension
f
Method 1
Compress it 4 times.
5 mm
f
Method 2
Compress it 4 times.
5 mm
Extending the power cable