![Samsung AC NX S C Series Installation Manual Download Page 14](http://html.mh-extra.com/html/samsung/ac-nx-s-c-series/ac-nx-s-c-series_installation-manual_336654014.webp)
AA
14
English
1-phase terminal block spec
AC power : M4 screw
Communication : M4 screw
1(L) 2(N)
N
L
11.4
11.4
10.1
10.1
When installing the indoor unit in a computer room or net work room, use the double shielded (Tape aluminum / polyes-
ter braid + copper ) cable of FROHH2R type.
Indoor Power supply
Communication Cable
Home Server
Power Supply
Max/Min(V)
Indoor Power cable
220-240V~, 50Hz
±10%
1.5mm²
↑
,3wires
0.75-1.5mm²,2wires
0.75mm²,2wires
Between Indoor and Outdoor Connection cable Specifications(Common in use)
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
11.4
10.1
3-phase terminal block spec
AC power : M4 screw
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
9.95
11.55
Communication : M4 screw
Connecting the cable