EB 8389-1S EN
105
Appendix
Message
Possible reasons
Recommended action
Status
classification Single reset
Defective actuator
springs
−
The actuator spring pre-loading
is reduced.
−
Check actuator springs.
•
[ ]
•
Supply pressure status
−
The supply pressure is outside
permissible limits.
−
Check supply pressure.
•
[ ]
•
−
The supply pressure is too high.
•
[ ]
−
The supply pressure fluctuates.
•
[ ]
−
The supply pressure is too low.
•
[ ]
−
No supply pressure is available.
•
[ ]
Diagnostics > Monitoring > Valve position
Manipulated variable
range limitation
−
The working range is limited at
upper or lower range value.
−
The valve is jammed.
−
Check that pneumatic installa-
tions and connections are tight.
−
Check supply pressure.
−
Check plug stem for external in-
fluences that could be blocking
it.
•
[ ]
•
Course of end position
−
Course of end position mono-
tonically increasing/decreasing.
−
The course of end position
alternates.
−
Check seat and plug.
•
[ ]
•
Positioner-valve linkage
−
No optimal travel transmission.
−
The working range is limited.
−
Check attachment.
•
[ ]
•
Manipulated variable
range
−
The working range is mainly
close to the CLOSED/max.
OPEN position.
−
The working range is mainly in
the CLOSED/max. OPEN
position.
−
Rethink the working range.
•
[ ]
•
Appendix