48* Diagnostic parameters
d0 Temperature
Read only
Current operating temperature [°C] inside the positioner (accuracy
±3 %)
d1 Min. temperature
Read only
Lowest temperature [°C] recorded inside the positioner since start-
ing the operating hours counter
d2 Max. temperature
Read only
Highest temperature [°C] recorded inside the positioner since start-
ing the operating hours counter
d3 No. of zero calibra
-
tions
Read only
The number of zero calibrations performed since last initialization
d4 No. of initializations
Read only
Number of initializations performed since last start with default
values
d5* Zero limit
0.0 to 100.0 %,
[5.0 %] of the nominal
range, ESC
Valve position limit relating to nominal range
'Zero point' message (Code 58) triggered depending on selected
status classification if limit is exceeded.
Note:
The 'Zero point' message (Code 58) has the default status
classification 'Maintenance required'. This classification can only
be changed in the operator software (e.g. TROVIS-VIEW).
d6 Condensed state
Read only
Summary of all status messages classified according to NAMUR
Recommendation NE 107
OK: No message
C: Maintenance required
CR: Maintenance demanded
S: Out of specification
B: Failure
I: Function check