EB 8389-1S EN
17
Monitoring
2.1.2
Condensed state
To provide a better overview on the condi-
tion of the positioner, all status messages are
summarized in a condensed state which is
made up from a summary of all classified
messages in the positioner. The status mes-
sage with the highest priority determines
which condensed state is set.
The condensed state appears in TROVIS-
VIEW 4 on the right-hand side of the info
bar and in the
Measured process values
folder. See
u
Table 3 for a description of the
icons and their meaning.
Additionally, the condensed state can be
used to trigger the data logger. See
u
Note:
The condensed state is marked by
until the positioner data have been up-
loaded.
The condensed state can be read in the posi-
tioner display in Code 48 - d6. See
u
Condensed state at the fault alarm output
The condensed state also be read out at the
fault alarm output if one of the following
conditions occurs:
1.
Condensed state 'Failure' is activated.
2.
Condensed state 'Function check' is acti
-
vated and the fault alarm output is acti-
vated.
3.
Condensed state 'Maintenance required'
or 'Out of specification' is activated and
the fault alarm output is activated.
Table 3:
Condensed state reading
Status message
TROVIS-VIEW 4/DTM
Positioner
Priority
Failure
red
Function check
orange
Text e.g. TESTING, TUNE or
TEST
Out of specification
yellow
blinking
Maintenance request/
maintenance required
blue
No message, OK
green