System code number 1
Weather-compensated heating control system without drinking water heating
4
In rated operation, the heating circuit cir-
culation pump (HCP) is running. The flow
temperature set point value is determined
according to the gradient of the heating
characteristic or a 4-point setting of the
heating characteristic, see chapter 5.4.1
4
In reduced operation, the heating circuit
circulation pump (HCP) is running. The
flow temperature set point is reduced by
the set back difference(s), see chapter
5.4.2
30
EB 5431 EN
System descriptions
F
RF
RS
OS
FS1
HCP
RfS
Fig. 3
⋅
System code number 1