Code
no.
Parameter
– Display, values
[default setting]
Description
Note:
Codes with marked with an asterisk (*) must be enabled with Code
3
prior to configuration.
14* Setpoint cutoff decrease
(final position w <)
0.0 to 49.9 [1.0] %
No · ESC
If reference variable w reaches the percentage adjusted that
causes the valve to close, the actuator is immediately completely
vented (with AIR TO OPEN) or filled with air (with AIR TO
CLOSE). This action always lead to maximum tight-closing of the
valve.
Codes
14/15
have priority over Codes
8/9/10/11
.
Codes
21/22
have priority over Codes
14/15
.
15* Setpoint cutoff increase
(final position w >)
[No]
50.0 to 100.0 %
ESC
If reference variable w reaches the percentage adjusted that
causes the valve to open, the actuator is immediately completely
filled with air (with AIR TO OPEN) or vented (with AIR TO
CLOSE). This action always lead to the valve being completely
opened.
A signal pressure limit is possible over Code
16
.
Codes
14/15
have priority over Codes
8/9/10/11
.
Codes
21/22
have priority over Codes
14/15
.
Example:
Set the cutoff to 99 % for three-way valves.
16* Pressure limit
[No]
P 1.4 · 2.4 · 3.7
ESC
The signal pressure to the actuator can be limited in stages.
After changing a pressure limit already set, the actuator must be
vented once (e.g. by selecting the fail-safe position (SAFE) over
Code
0
).
NOTICE
Do not activate the pressure limit for double-acting actuators with
fail-safe position AIR TO OPEN (AtO).
17* Proportional-action
coefficient KP (step)
0 to 17 [7]
ESC
Displaying or changing the K
P
and T
V
steps:
During initialization, the K
P
and T
V
values are optimized. Should
the positioner show a tendency for impermissibly high post-pulse
oscillation due to additional interference, the K
P
and T
V
steps can
be adapted after initialization. For this, either the T
V
step can be
increased in increments until the desired response behavior is
reached or, when the maximum value of 4 is reached, the K
P
step can be decreased in increments.
Note:
Changing the K
P
step influences the system deviation.
18* Rate time TV (step)
[2]
1 3 4 No
ESC
Changing T
V
, see Code
17
.
Note:
Changing the T
V
step has no effect on the system devia-
tion.
EB 8387-3 EN
69
Code list