Blocking position
Default: 0
Turn
→
Code
34
Press
, Code
34
blinks.
Turn
→
Closing direction (CCL counter-
clockwise/CL clockwise)
Press
Turn
→
Code
35
Press
, Code
35
blinks.
Turn
→
Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Press
Start initialization:
Initialization
Fail-safe position setting
Progress indicated until
initialization starts
Blocking position
Turn
→
Code
0
Press
, Code
0
blinks.
Turn
→
Init
Press
. The setting of the fail-safe posi-
tion
AtO
or
AtC
appears.
Keep
pressed down for 6 seconds.
Initialization starts after the progress indica-
tion has stopped.
The operating mode changes to
MAN
.
The blocking position appears.
Note:
As initialization has not been carried
out completely, the error code
76
(no emer-
gency mode) and possibly also error code
57
(control loop) may appear on the dis-
play.
These messages do not influence the
positioner’s readiness for operation.
Cancel the blocking position and change to
automatic mode
(AUTO):
For the positioner to follow its reference
variable again, the blocking position must
be canceled and the positioner must be set
to automatic operating mode.
Turn
→
Code
1
Press
, Code
1
and the
icon blink.
Turn
until the pressure in the positioner
builds up and the valve moves slightly past
the blocking position.
Press
to cancel the blocking position.
Turn
→
Code
0
Press
, Code
0
blinks.
Turn
→
AUtO
EB 8387-3 EN
57
Start-up – Settings
mm
%