7
Start-up – Settings
WARNING!
Attach the positioner, keeping the following
sequence:
1. Mount the positioner on the control valve
2. Connect the supply air
3. Connect the electrical power
4. Perform the start-up settings
Reading on display after connecting the
electrical auxiliary power:
4
tEStinG
runs across the display and then
and
blink on the display when
the positioner has
not yet been initial-
ized
. The reading indicates the lever po-
sition in degrees in relation to the longi-
tudinal axis.
Reading when the
positioner has not yet
been initialized
4
Code
0
appears on the display when a
positioner has been
initialized
. The
positioner is in the last active operating
mode.
WARNING!
The actuator stem moves while the start-up
settings are being performed.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
46
EB 8387-3 EN
Start-up – Settings
Assignment of dynamic HART
®
variables
Variable
Meaning
Unit
Set point
%
Direction of action set point
%
Set point after transit time specification
%
Valve position
%
Set point deviation e
%
Absolute total valve travel
–
Binary input
status
0 = Not active
1 = Active
255 = –/–
–
Internal
solenoid
valve/forced
venting status
0 = De-energized
1 = Energized
2 = Not installed
–
Condensed
state
0 = No message
1 = Maintenance
required
2 = Maintenance
demanded
3 = Failure
4 = Out of
specification
7 = Function check
–
Temperature
°C