Press
display:
MAN
, Code
0
blinks.
Turn
→
Init
Press
The setting of the fail-safe position
AtO
or
AtC
appears.
Keep
pressed down for 6 seconds.
Zero calibration is started, the positioner
moves the control valve to the CLOSED posi-
tion and recalibrates the internal electrical
zero point.
7.7
Reset to default values
This function resets all start-up parameters
and diagnosis data to their default values
(see code list in section 11).
Enable configuration:
Turn
→
Code
3
, display:
No
Press
, Code
3
blinks.
Turn
→
YES
Press
, display:
Reset start-up parameters:
Reset
Default: No
Turn
→
Code
36
, display:
••–••–
Press
, Code
36
blinks.
Turn
→
Std
Press
. All start-up parameters and diag-
nosis data are reset to their default values.
Note:
Code
36 - diAG
allows just the diag-
nosis data (EXPERTplus) to be reset. Refer to
EB 8389 on EXPERTplus valve diagnostics.
EB 8387-3 EN
59
Start-up – Settings