EB 6132 EN
9-1
Servicing
9
Servicing
The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.
Risk of fatal injury due to electric shock
(devices with 230 V supply voltage).
Î
Before connecting wiring, performing
any work on the device or opening the
device, disconnect the supply voltage
and protect it against unintentional re-
connection.
Î
Only use power interruption devices that
are protected against unintentional re-
connection of the power supply.
The device was checked by SAMSON before
it left the factory.
− The product warranty becomes void if
service or repair work not described in
these instructions is performed without
prior agreement by SAMSON's After-sales
Service.
−
Only use original spare parts by
SAMSON, which comply with the original
specifications.
9.1
Tuning zero and span
The
ZERO
and
SPAN
potentiometers are ac-
cessible on the front panel.
SAMSON 6132
p/i Converter
Model 6132-
Var.-ID
Serial no.
Input
0utput
Power supply
Made in Germany
SAMSON AG D-60314 Frankfurt
0
1
2
3
4
5
6
7
ZERO potentiometer
SAMSON 6132
p/i Converter
Model 6132-
Var.-ID
Serial no.
Input
0utput
Power supply
Made in Germany
SAMSON AG D-60314 Frankfurt
0
1
2
3
4
5
6
7
SPAN potentiometer
Î
Disconnect the supply voltage and pro-
tect it against unintentional reconnection.
Î
Remove any lines to upstream compo-
nents (pneumatic input signal) and any
wires to downstream control equipment
(electric output signal).
Î
Connect the pneumatic input to a pres
-
sure instrument and the electric output to
a measuring instrument with sufficient
accuracy.
Î
Switch on supply voltage.
Î
Tune zero:
Î
Set the input signal to 0.2 bar.
The output signal of the measuring
instrument must now indicate
0/4 mA or 0/2 V.
Î
Correct deviations at the
ZERO
potentiometer.
Î
Tune span:
Î
Raise the input signal from 0.2 bar to
1 bar.
The output signal of the measuring
instrument must now indicate 20 mA
or 10 V.
Î
Correct deviations at the
SPAN
po-
tentiometer.
DANGER
!
Note
Summary of Contents for 6132
Page 10: ...2 2 EB 6132 EN...
Page 14: ...3 4 EB 6132 EN...
Page 20: ...5 4 EB 6132 EN Installation...
Page 22: ...6 2 EB 6132 EN...
Page 24: ...7 2 EB 6132 EN...
Page 30: ...10 2 EB 6132 EN...
Page 32: ...11 2 EB 6132 EN...
Page 34: ...12 2 EB 6132 EN...
Page 36: ...13 2 EB 6132 EN...
Page 39: ...EB 6132 EN 14 3...
Page 40: ...14 4 EB 6132 EN...
Page 42: ...15 2 EB 6132 EN...
Page 43: ......