Installation
5.5
Electrical connection
Risk of fatal injury due to electric shock (de-
vices with 230 V supply voltage).
Î
Before connecting wiring, performing
any work on the device or opening the
device, disconnect the supply voltage
and protect it against unintentional re-
connection.
Î
Only use power interruption devices that
are protected against unintentional re-
connection of the power supply.
For electrical installation, observe the rele-
vant electrotechnical regulations and the ac-
cident prevention regulations that apply in
the country of use. In Germany, these are
the VDE regulations and the accident pre
-
vention regulations of the employers’ liability
insurance.
The terminals of the converter are designed
for wires with 0.5 to 2.5 mm².
Î
Connect the wires of the converter to the
terminals.
Route the connecting lines for supply
voltage and output signal separately.
L/+ N/-
-32 +31
–
+
PE
N/-
L/+
Power supply
Output
Information on old device versions:
Old converter versions (device index 01, with
DMS sensor, until 1998) have a different
terminal assignment compared to the new
versions (device index 02). The old and new
device covers are not interchangeable as a
result.
Observe new terminal assignment when
replacing devices.
Fig. 5-1:
Electrical connection
5.6
Pneumatic connection
Risk of converter damage due to the maxi-
mum pressure at the converter input being
exceeded.
The maximum permissible pressure at the
converter input is restricted to 2 bar.
Î
Make sure that the input signal does not
exceed 2 bar.
Air quality requirements
Î
Only use air that is dry and free of oil
and dust.
Î
Observe the air quality according to
ISO 8573-1: 2001.
Î
Blow through all air pipes and hoses
thoroughly before connecting them.
DANGER
!
NOTICE
!
NOTICE
!
Summary of Contents for 6132
Page 10: ...2 2 EB 6132 EN...
Page 14: ...3 4 EB 6132 EN...
Page 20: ...5 4 EB 6132 EN Installation...
Page 22: ...6 2 EB 6132 EN...
Page 24: ...7 2 EB 6132 EN...
Page 30: ...10 2 EB 6132 EN...
Page 32: ...11 2 EB 6132 EN...
Page 34: ...12 2 EB 6132 EN...
Page 36: ...13 2 EB 6132 EN...
Page 39: ...EB 6132 EN 14 3...
Page 40: ...14 4 EB 6132 EN...
Page 42: ...15 2 EB 6132 EN...
Page 43: ......