Annex A (configuration instructions)
16.4
Blockage
16.4.1
Blockage detection
The positioner can only detect a valve blockage after either an initialization ('Start-up and
configuration' section) or a transit time measurement ('Service' folder in 'Start-up' or 'Func
-
tions') has been performed after the actuator is started up for the first time.
The positioner detects a valve blockage
when the actuator stem extends
and with
absolute
travel adjustment
by comparing the travel after the limit switch has been triggered with the
travel measured on initialization. If the comparison shows that the limit switch was triggered
too early, this indicates that there is a valve blockage. The
red LED
blinks:
−
Blockage
On
Off
2
4
6
8
10
Time in s
Settings\Actuator\Blockage
Function
WE
Adjustment range
Blockage detection
No
No, Yes
16.4.2
Blockage removal
When the
Blockage removal
function is active, the actuator stem extends and retracts 1 mm
at the adjusted stroking speed three times in sequence. The action is indicated by the
yellow
LED
(only when the
Blockage removal
function is active).
−
Removing blockage
On
Off
Time in s
Note
Summary of Contents for 5857
Page 6: ......
Page 12: ...1 6 EB 5857 EN...
Page 20: ...3 6 EB 5857 EN...
Page 44: ...8 12 EB 5857 EN Operation...
Page 48: ...10 2 EB 5857 EN...
Page 50: ...11 2 EB 5857 EN...
Page 52: ...12 2 EB 5857 EN...
Page 54: ...13 2 EB 5857 EN...
Page 56: ...14 2 EB 5857 EN...
Page 58: ...15 2 EB 5857 EN Certificates EU declaration of conformity...
Page 59: ...EB 5857 EN 15 3 Certificates TR CU certificate...
Page 60: ...15 4 EB 5857 EN Certificates...
Page 72: ...16 12 EB 5857 EN...
Page 76: ...17 4 EB 5857 EN...
Page 77: ......
Page 78: ......
Page 79: ......