16-2
EB 5857 EN
Annex A (configuration instructions)
16.2
Position feedback signal
The position feedback indicates the position of the actuator stem.
The span of the
position feedback signal
is adjusted over the lower and upper range value
parameters.
Settings\Inputs and outputs\Position feedback signal
Position feedback signal
WE
Adjustment range
Lower range value
0.0 V
0.0 V to 10.0 V
Upper range value
10.0 V
0.0 V to 10.0 V
16.3
Functions
16.3.1
Detect input signal failure
The positioner detects a failure of the input signal as soon as the value falls below the lower
range value by 0.3 V. An input signal failure is indicated in the 'Service' folder ('Statistics')
as well as by the
red LED
:
−
Input signal failure detected
On
Off
Time in s
The input signal failure can only be detected when at least 0.5 V is set as the lower range
value.
If the
Input signal failure
function is active, the reaction of the actuator upon failure of the in-
put signal is determined by the Positioning value upon input signal failure parameter.
−
'Positioning value upon input signal failure'
= Internal
The actuator stem moves to the position specified in the Internal positioning value param
-
eter upon failure of the input signal.
Note
Summary of Contents for 5857
Page 6: ......
Page 12: ...1 6 EB 5857 EN...
Page 20: ...3 6 EB 5857 EN...
Page 44: ...8 12 EB 5857 EN Operation...
Page 48: ...10 2 EB 5857 EN...
Page 50: ...11 2 EB 5857 EN...
Page 52: ...12 2 EB 5857 EN...
Page 54: ...13 2 EB 5857 EN...
Page 56: ...14 2 EB 5857 EN...
Page 58: ...15 2 EB 5857 EN Certificates EU declaration of conformity...
Page 59: ...EB 5857 EN 15 3 Certificates TR CU certificate...
Page 60: ...15 4 EB 5857 EN Certificates...
Page 72: ...16 12 EB 5857 EN...
Page 76: ...17 4 EB 5857 EN...
Page 77: ......
Page 78: ......
Page 79: ......