EB 5857 EN
16-3
Annex A (configuration instructions)
−
'Positioning value upon input signal failure'
= Last position
The actuator stem remains in the last position that the valve moved to before failure of the
input signal.
The error message is reset and the actuator returns to closed-loop operation if the input sig-
nal moves within 0.2 V of the lower range value.
Settings\Actuator\Functions
Functions
WE
Adjustment range
Detect input signal failure
No
Yes/No
Positioning value upon input signal failure
Internal
Internal, last position
Internal positioning value
0.0 %
0.0 to 100.0 %
16.3.2
End position guiding
The actuator stem moves to the end positions earlier if the
end position guiding
function is
active:
−
'End position guiding when the value falls below the limit'
The actuator stem moves to the 0 % position when the input signal falls below 'Value
below limit (end position guiding)'.
−
'End position guiding when the value exceeds the limit'
The actuator stem moves to the 100 % position when the input signal exceeds 'Value
above limit (end position guiding)'.
When 'End position guiding (stem extends)' = 0 % and 'End position guiding (stem retracts)'
= 100 %, the end positioning guiding function is deactivated.
Settings\Actuator\Functions
Functions
WE
Adjustment range
End position guiding (stem extends)
1.0 %
0.0 to 49.9 %
End position guiding (stem retracts)
97.0 %
50.0 to 100.0 %
Note
Summary of Contents for 5857
Page 6: ......
Page 12: ...1 6 EB 5857 EN...
Page 20: ...3 6 EB 5857 EN...
Page 44: ...8 12 EB 5857 EN Operation...
Page 48: ...10 2 EB 5857 EN...
Page 50: ...11 2 EB 5857 EN...
Page 52: ...12 2 EB 5857 EN...
Page 54: ...13 2 EB 5857 EN...
Page 56: ...14 2 EB 5857 EN...
Page 58: ...15 2 EB 5857 EN Certificates EU declaration of conformity...
Page 59: ...EB 5857 EN 15 3 Certificates TR CU certificate...
Page 60: ...15 4 EB 5857 EN Certificates...
Page 72: ...16 12 EB 5857 EN...
Page 76: ...17 4 EB 5857 EN...
Page 77: ......
Page 78: ......
Page 79: ......