9.2 "CHECK_BACK" messages
Bit
no.
Name
Description
R
= static message, remains valid while the error is present in the field device
A
= dynamic message, automatically reset when read
0
CB_FA IL_SA VE
Fail-safe position
The fail-safe position was activated by the device, either by selecting operating
mode "OUT OF SERVICE", by activating the forced venting function, or by a
communication failure.
The device switches to "OUT OF SERVICE" mode.
R
1
CB_REQ_LOC_OP
Request for local operation
Set when local operation was requested, but not enabled (LOCAL_OP_ENA = 0).
A
2
CB_LOC_OP
Local operation
R
3
CB_OVERRIDE
Emergency operation / forced venting active
Forced venting was activated, i.e. the signal applied to ter81 and 82 is
smaller than 3 V. The control valve moves to fail-safe position regardless of the
control loop.
Automatically reset when a 6 to 24 V DC signal is applied to ter81 and 82.
R
6
CB_ZERO_ERR
Zero point error
Displayed when "manufacturer specific" was set for "Selection identification
number". Message indicated by bit 8 of the DIAGNOSIS parameter, see section 9.3.
7
CB_TRAV_TIME
Status of travel monitoring
Set when permissible transit time was exceeded.
A
10
CB_UPDATE_EVT
Change of static data
Set when device data are changed. Enables monitoring of
(unintentional/unauthorized) changes of the initially adjusted values.
A
11
CB_SIMULATE
Simulation mode
, i.e. values are not derived from the process.
Set when the device is in simulation mode. In this case, the controlled variable x is
predetermined.
R
13
CB_CONTR_ERR
Internal control loop error
Displayed when the positioner is unable to control the adjusted range of tolerance
for error messages within the preset delay time.
Possible sources of error:
Oscillation caused by actuator operated too rapidly (small travel volume)
Remedy: Reduce supply air pressure as described in section 3.1.2 or install a
signal pressure throttle.
Supply air failure/insufficient supply air Filter is clogged
Solenoid valves are oiled
Actuator diaphragm is ruptured
Actuator springs are broken
Control valve is blocked
Considerable increase in friction at the control valve
Message is indicated by bit 7 and bit 13 of the CHECK_BACK parameter (see table
on pages 42/43).
Status of bit 7 is reset automatically. Bit 13 is reset via "SELF_CALIB_CMD = 10"
(resetting control loop error)
R
68
EB 8382-2 EN
Messages and diagnosis