5-2
EB 8072 EN
Installation
easily access the device from the work posi
-
tion.
Pipeline routing
The inlet and outlet lengths (see Table 5-1)
vary depending on several variables and
process conditions and are intended as rec
-
ommendations. Contact SAMSON if the
lengths are significantly shorter than the rec-
ommended lengths.
To ensure that the valve functions properly,
proceed as follows:
Î
Observe the recommended inlet and
outlet lengths (see Table 5-1). Contact
SAMSON if the valve conditions or states
of the medium process deviate.
Î
Install the valve free of stress and with the
least amount of vibrations as possible.
Read information under ‘Mounting posi-
tion’ and ‘Adjusting the packing’ in this
section.
Î
Install the valve allowing sufficient space
to remove the actuator and valve or to
perform service and repair work on
them.
Mounting position
Generally, we recommend installing the
valve with the actuator upright and on top of
the valve.
In the following versions, the valve must be
installed with the actuator on top:
− Valves in NPS 4 and larger
−
Valves with insulating section for low
temperatures below –10 °C (14 °F)
Î
Contact SAMSON if the mounting posi-
tion is not as specified above.
Support or suspension
The plant engineering company is responsi-
ble for selecting and implementing a suitable
support or suspension of the installed control
valve and the pipeline.
Depending on the valve version and mount
-
ing position, the valve, actuator and pipeline
must be supported or suspended.
Valves, which are not installed in the pipe
-
line in the upright position with the actuator
on top, must be supported or suspended.
Valve accessories
Î
During connection of valve accessories,
make sure that they are easily accessible
and can be operated safely from the
work position.
Vent plugs
Vent plugs are screwed into the exhaust air
ports of pneumatic and electropneumatic de
-
vices. They ensure that any exhaust air that
forms can be vented to the atmosphere (to
avoid excess pressure in the device). Further-
more, the vent plugs allow air intake to pre
-
vent a vacuum from forming in the device.
Î
Locate the vent plug on the opposite side
to the work position of operating person
-
nel.
Note
Summary of Contents for 3291
Page 14: ...1 10 EB 8072 EN...
Page 30: ...4 6 EB 8072 EN Shipment and on site transport...
Page 56: ...8 4 EB 8072 EN...
Page 82: ...12 2 EB 8072 EN...
Page 84: ...13 2 EB 8072 EN...
Page 86: ...14 2 EB 8072 EN...
Page 87: ...EB 8072 EN 14 3...
Page 88: ...14 4 EB 8072 EN...
Page 91: ...EB 8072 EN 15 3 Annex...
Page 95: ......