Type 3374 Actuator
1. Remove the housing cover.
2. Route the connecting cables through the
cable entries onto the terminals and fas-
ten them.
Connect the control signals of the con-
troller to the connections
eL
and
aL
:
4
If voltage is applied to
eL
, the actua-
tor motor retracts the actuator stem
into the actuator (”Actuator stem re-
tracts“).
4
If voltage is applied to
aL
, the actu-
ator stem is extended (”Actuator
stem extends“).
Actuators operated in parallel must be
controlled using separate contacts as us-
ing one common on/off contact can
cause the actuators to oscillate in the end
positions.
3. Remount the housing cover.
EB 5868-1 EN
9
Electrical connections
aL
eL
N
N
L
N
+
–
L
N
eL
aL
Ce
Ce
L
41
44
42
51
54
52
81
82
83
91
92
93
Fig. 2 · Electrical connection of Type 3374-10 with three-step signal
retracts
extends
Magnet in version with fail-safe function
(not Type 3374-10)
Potentiometer (optional)
Summary of Contents for 3214