Type 3274 Actuator
1. Remove the housing cover on the side.
2. Route the connecting cables through the
cable entries on the housing onto the ter-
minals and fasten them.
Voltage must always be applied to termi-
nals N and L. If no supply voltage is ap-
plied, the actuators will remain in their
last position. Actuators with fail-safe
function will move to their fail-safe posi-
tion.
3. Connect grounding conductors to the
separate grounding conductor terminals
on the inside of the housing.
4. Remount the housing cover.
Fuse:
The PCB of the motor’s electronics includes a
bracket with a 5 x 20 mm glass tube fuse:
for 230 V, 50 Hz = T 1 (1 A, time-lag)
for 110 V, 50 Hz = T 1.25 (1.25 A, time lag)
for 24 V, 50 Hz = T 6.3 (6.3 A, time-lag)
10
EB 5868-1 EN
Electrical connections
N
L
aL eL a43 e53
81
1.311.321.33 2.312.32 2.33
e
a
a
e
"e"
"a"
1
2
4
M
F
F
e
a
PE
N
L
3274-11...-18,-21,-23
3274-13,-14,-17,-18,-22
ϑ
Fig. 3 · Electrical connection of Type 3274 with three-step signal
Safety interlock circuit,
only for Type 3274-2x
Controller
Note!
The controller output relays used to control the
input signals aL (stem extends) and eL (stem
retracts) must be operated and connected
using terminal 81 (same potential) only.
Heating
resistor
Retracts
Extends