4. TROUBLESHOOTING GUIDELINE
Please see the table below if you experience any problems with the Elogic DC battery charger
and/or the installation.
Problem
Possible cause
Remedy
Elogic DC is not working
at all.
No input voltage.
Check wiring and input fuse.
Input voltage is too low.
Check input voltage, adjust
the input voltage settings,
start engine.
No positive signal on main
On/Off control wire.
Check wiring, fuses and
status of engine run signal.
Positive signal on BMS input.
Check output battery
BMS status.
Very poor input battery
condition.
Replace battery.
The battery is not being
charged up to it’s maximum
capacity.
Incorrect absorption charge
voltage setting.
Check the battery type
selection for correct setting.
Or adjust the absorption
voltage.
Incorrect charge current
setting.
Make sure that the maximum
output current setting is
at maximum level (check
if allowed by battery
manufacturer).
Too much voltage loss
in battery cables and/or
connections.
Make sure that the battery
cables have a large enough
diameter. Check if all DC
connections are solidly made.
Additional battery loads are
consuming too much current
during charging.
Turn-off or disconnect all
battery loads.
Charge current is too low.
High ambient temperature.
Try to lower the ambient
temperature around the
charger.
Charger is operating in the
absorption charging stage.
Do nothing. The battery is
almost fully charged and
consumes less current by
itself.