Note related to B1 batteries:
(b1) device with a more powerful charger, which does
not have a battery pack, nor the possibility of in-
stalling them in the same box.
If an accumulator module is required, it will need
to be ordered as a separate item, which will be
connected to the UPS using the supplied cable.
before connecting a module or group of batteries to the
device or another available module,
it is necessary
to check
that the voltage value printed on the back of
the device next to the battery connector is appropriate
and that the polarity between the means of connection
corresponds.
for more information, see Chapter 9 of this document.
4.3. operaTing prinCiple.
This user manual describes the installation and mode of opera-
tion of SPS AdvAnCe R and SPS AdvAnCe T series UPSs indi-
cated in Tab. 1 and Tab. 2.
These line-interactive pure sine-wave output devices are de-
signed to protect your most sensitive electronic devices against
power supply problems including undervoltages, spikes, pro-
longed voltage drops, line noise and mains failures.
with the device running and the mains supply correct, the load
or loads are powered through the stabiliser featuring buck-
boost technology. Any possible variations in the input voltage
are corrected by the stabiliser module while they are within its
regulation range.
with mains supply absent or voltage and/or frequency outside
the range, the load or loads will be powered from the batteries
through the inverter for a certain period of time depending on
the model, battery charge level and load itself connected to
the output.
when plugged into an AC socket, the batteries are set to charge
mode regardless of whether the device is on or off.
In SPS AdvAnCe T 1000 to 3000 vA models, it is possible to
increase the standard backup of the devices by connecting ad-
ditional modules and/or optimising the recharge time of the ac-
cumulators by incorporating higher performance chargers (b1).
The entire power range of SPS AdvAnCe R and T models ena-
bles:
•
Serial port for communication and control of the device. The
serial port supports communications directly with a server
and the protocol is in accordance with an RS232 interface.
SPS AdvAnCe T models also have an additional USb serial
port for communication and control of the device. It is not
possible to use the RS232 and USb ports at the same time.
•
An ePo connector for optional, external installation by the
user of an emergency stop button.
•
A smart slot in which one of the following communication
cards can be installed:
Integration into computer networks using an SnmP
adapter.
4.3.1. operating diagram
N
f
N
f
AC input
Input
filter
electronic stabiliser
(buck-boost)
output
relay
AC
output
Charger
batteries
Inverter
Fig. 6.
Operating diagram.
4.3.2. notable features.
•
Pure sine-wave output waveform, suitable for all types of
load.
•
Possibility of starting the device without mains power (cold
start).
•
great adaptability to the worst conditions of the mains.
wide input voltage, frequency and waveform ranges, thus
avoiding excessive dependence on limited battery power.
•
If mains supply is present and voltage and frequency are
within the range, the built-in stabiliser featuring buck-boost
technology powers the loads.
•
Compatibility with APfC loads.
The vast majority of power supplies for electronic devices
are switched-mode (SmPS) and they are increasingly being
equipped with active power factor correction (APfC) to
minimise distortion caused to the electrical line. SPS home
UPSs are compatible with all devices that incorporate these
functionalities.
•
Possibility of fast and easy backup extension by adding bat-
tery modules
(1)
.
•
Availability of additional battery chargers to reduce battery
recharge time (b1)
(1)
.
•
Intelligent battery management technology is very useful
for extending the life of accumulators and optimising re-
charge times.
•
Control panel with LCd display available on all models.
•
Remote emergency power off control (ePo).
•
Serial communication port: RS232 and USb
(1)
.
•
Availability of optional connectability cards to improve
communication capabilities.
•
Protection against overload, short circuit and overtempera-
ture.
(1)
only in SPS AdvAnCe T models.
Model
Type
Input/output type
SPS 750 ADV R
Standard
Single-phase / Single-phase.
SPS 1000 ADV R
SPS 1500 ADV R
Tab. 1.
SPS ADVANCE R standardised models.
SPS ADVANCE R & T
UnInTeRRUPTIbLe PoweR SUPPLy (UPS)
USER MANUAL