24
SALICRU
9. ANNExES.
9.1. general TeChniCal speCifiCaTions.
Models.
ADVANCE R
Available power ratings (VA / W).
750VA / 450W
1000VA / 600W
1500VA / 900W
Technology.
Line-interactive with sine-wave output.
Input.
Input type.
Single-phase.
number of cables.
3 cables - Phase R (L) + neutral (n) and earth.
Rated voltage.
220 / 230 / 240 v AC
Input voltage range.
165..290 v AC
Input frequency range.
50 / 60 hz (auto-detectable).
Inverter.
waveform.
Pure sine wave.
Power factor.
0.6
Rated voltage.
220 / 230 / 240 v AC
output voltage accuracy (battery mode).
±10%
Total harmonic distortion (Thdv), with linear load.
< 5 % linear load
<10 % non-linear load
frequency.
50 / 60 hz.
with mains absent -backup mode- 50 / 60 ±1% hz.
Transfer time, line mode to battery mode (normal mode).
4 ms
Compatibility with APfC loads.
yes
Performance at full load, in normal mode
with battery 100% charged.
> 95 %
Performance at full load, in battery mode.
> 78 %
> 80 %
overload in line mode
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
overload in battery mode.
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
Batteries (AGM sealed 3 - 5 years life).
element voltage.
6 v dC
Capacity.
9 Ah
7 Ah
9 Ah
number of batteries in device connected in series / group voltage.
2 / 12 v dC
4 / 24 v dC
Low battery voltage.
11.7 v
22.2 v
blocking voltage for group end of backup.
10.5 v
20.5 v
Internal battery charger.
group floating voltage.
13.65 v
27.5 v
maximum charge current.
1 A
Recharge time.
4 hours to 90%
Other functions.
Cold start.
yes
emergency power off (ePo).
yes
General.
IeC input connectors.
IeC 60320 C14 10A
IeC output connectors.
IeC 60320 C13
Communication ports.
(RS232 - db9).
Connector for external ePo installation
yes
Slot for optional cards.
SnmP
monitoring software.
Powermaster (free download).
Audible noise at 1 m in battery mode.
< 40 db
operating temperature.
0..+40ºC
Storage temperature with batteries.
–20..+50 ºC
Storage temperature without batteries.
–20..+70 ºC
working altitude.
2,400 masl (power degradation up to 5,000 m)
Relative humidity.
0..90 % non-condensing.
Protection rating.
IP20
dimensions (mm) depth x width x height.
216x433x44 (1 U)
485x433x44 (1 U)
weight (kg).
8.6
14.2
16.2
Safety.
en IeC 60950-1
en IeC 60240-1
electromagnetic compatibility (emC).
en IeC 60240-2