39
Smarty 3X VE / Smarty 3X VE 3.0
www.salda.lt
11.1. „min_0V“ - {0ppm-2000} %, Pa
11.2. „max_10V“- {0ppm-2000} %, Pa
12. „CO2“ - when CO2 control is selected, min. and max. limits are set for the CO2 converter
12.1. „min_0V“ - {0ppm-2000} %, ppm
12.2. „max_10V“- {0ppm-2000} %, ppm
12.3. „PPM_100%“ - {20-255}*100ppm
13. „VentCtrl“ - setting of the indications for fans
13.1. „SAF“ - {Percent, Pressure} settings for the indications of the supply air motor %, Pa.
13.2. „EAF“ - {Percent, Pressure, SAF+Percent} settings for the indications of the extracted air motor %, Pa
SAF+Percent – the alteration of the extracted motor can change only at set value according to the supply.
13.3. „CO2“- {On/Off} extracted air CO2 sensor
13.4. „ResetToFactorySettings“ - after switching “OK”, factory settings are saved.
NOTICE! The unit and the controller reloads.
14. „Misc“ - stop conditions for the unit depending on the connection of the controller
14.1. „RC NC“ - {On, Off}
On – ( Remote Control ) No controller, the unit is stopped
Off – ( Remote Control ) No controller, the unit is on
This setting is not applicable if the unit is controlled via ModBus interface.
14.2. „F Timer“ - {On, Off}
On – ( Filters timer ) filter contamination timer on. Item „Filters“ appears on the main menu of the user.
Off – ( Filters timer ) filter contamination timer off.
14.3. „AX“ - {0, 1}
0 – overheat protection NC
1 – contactor malfunction protection indication
14.4. „Fans On“ - {On, Off}
On –in case of „AX“ protection, fans work at maximum speed.
15. „AF“ - anti-frost security settings
15.1. „AF detect“- {Off, DewP/PlateT, Toutside, Tesetpoint, Klingb, Heatex}for choosing anti-frost security algorithm type.
DewP/PlateT – according to the dew point and the heat exchanger wall temperature calculation algorithm
Toutside – according to outdoor sensor (DIBT)
TEsetpoint – according to exhaust air sensor
Klingb – according to Klinberger (hexagon) heat exchanger anti-frost diagram.
Heatex – according to Heatex (quadrangular) heat exchanger anti-frost diagram.
15.2. „FanReduc.“ - {On, Off} supply fan speed deceleration
On –allowed
Off – forbidden
15.3. „Bypp/Rot“- {On, Off}on activation of anti-frost protection.
On –possible to open the bypass valve o to stop the rotor.
Off –impossible to open bypass valve or stop the rotor.
15.4. „PassiveTC“ - {Off, 16,5°C}alarm report supplying low temperature air according to time set in 15.5.
15.5. „Excercise“ - {Off, 1-12h}how much time it is possible to supply low temperature air till the alarm report.
Off – only when temperature falls till „PassiveTC“ (see.:15.4).
16. „AF1“ –Anti-frost protection settings
Selecting 15.1. „AF detect“ - „DewP/PlateT“
16.1. „PlateTemp“ - 1°C – {-5 +10 °C}heat exchanger humidity temperature
Selecting 15.1. „AF detect“ - „Toutside“
16.1. „OutDoorTemp“ -
Selecting 15.1. „AF detect“ - „Tesetpoint“
16.1. „ExhaustTemp“ - {-20 +15 °C}when exhaust air temperature falls below the set value - anti-frost protection starts according to exhaust
air temperature.
16.2. „RotorPWM“ – rotor impulse width modulation percentage.
16.3. „DefrStpTime“ – rotor standing/defrosting time in minutes.
16.4. „PassiveTemp“ – outdoor air temperature value, in case of exceeding which, anti-frost function is allowed.
17. „CONF1“ - (only from V2.3 controllers‘ versions)
17.1. „CONF1“ - {„Ver X.2“, “Ver X.3“}
“Ver X.3“ – for turning on „DIBT“ and „Passive house“ functions.
It is possible to choose „Building protection“ unit‘s working mode,
No speed choice „Stop“, ( at „Schedules“ as well)
Necessary to set „Menu“ → „Extra“ → “Service” → “Menu configuration”
Necessary to set „Menu“ → „Menu configuration“ → „Economic temper.“
17,2 „3dayRH mean“ –for setting three-day humidity average %
17,3 „3dayRHCurr“ – three-day average of humidity %
17,4 „3dayOUTCurr“ - three-day average of outdoor air °C
17.5. „St/Sp time“ - External timer delay time for unit‘s switch to another mode.
18. „CONF2“ - (for controllers with V2.4.1. and higher)
18.1. „Old RC compatib“ - {*On“, „Off“} – compatibility with older remote controllers.
„On“ – the controller works with UNI, PRO, TPC and FLEX remote controllers but doesn‘t support extended ModBus address list.
„Off“ – controller works with FLEX remote controller and supports extended ModBus address list.
18.2. „empty1“ - unused
18.3.„empty2“ - unused
18.4. „empty3“ - unused
18.5.„empty4“ - unused