41
Smarty 3X VE / Smarty 3X VE 3.0
www.salda.lt
When using this remote control it is possible to activate functional nodes individually by selecting a relevant item.
Prior to activating the supply air heater or preheater, it is REQUIRED to switch on the supply air fan. All function, except for EC1
and EC2, are activated and deactivated by pressing the button “OK”.
Tested items
Activated output (in the control-
ler)
Activated output (in the controller)
LED
EC1 (V1)
V1-COM
Supply air fan speed (in percentage) is selected .
-
EC2 (V2)
V2-COM
Extract air fan speed (in percentage) is selected
-
Bypass 0-10
-
Not used
-
Cooling
X16-4, X16-8
NO contact closed (non-voltage).
-
X16-1, X16-3
Activated by remote control "V"
LED4 (atidaroma)
X16-2, X16-3
Deactivated by remote control
LED5 (uždaroma)
Heating
X16-30, X16-31
Supply air electrical heater. Relay K6
LED13
Rot.-Bypass
-
Damper opened, heat exchanger closed.
LED6 (atidaroma)
LED7 (uždaroma)
Fan Run (System
On)
X16-11 ir X16-12.
-
FanFail (System
Alarm)
X16-9, X16-10
-
Report slave ID
EC1 (V1)
%
Test
EC2 (V2)
%
Extra
Bypass 0-10
%
Cooling
Heating
Rot.-Bypass
Fan Run
Fan Fail
Extern. Fan
Pump
Outs. Damper
Extr. Damper
Preheater
Rotor fail
Overheat
Motor overheat
Exchanger
A3 Filter
Extern. Off
Fire input
Extract humidity
Supply air temp.
Extract air temp.
Outdoor air temp.
Exhaust air temp.
Water temperature
Extract CO2
External alarm