23
Smarty 3X VE / Smarty 3X VE 3.0
www.salda.lt
In the service menu there is an option to select parameters under which seasons change. 4 options are available: by three-day medium outdoor tem-
perature, by a date set in a calendar and there are separate manual switches for winter/summer seasons.
Operation:
This mode (when “winter” is indicated) impacts the restriction of the unit switch-off in winter. Normally, the unit can be off not longer than 2 h/day during
the winter season. 2 hours later the unit is switched on automatically and it operates according to the last settings.
Function adjustment, setting:
Only by “FLEX” remote control (password required)
Menu > Additional> Service > Seasons>Menu configuration>Seasons
• “Select a season” – select the parameter for changing seasons (default parameter – “3 day average”:
• 3 day average – by 3-day medium outdoor temperature (default temperature is 10°C).
• Calendar – by the set date, to be set
• Summer – manual switch-on of the summer season
• Winter – manual switch-on of the winter season
• “Settings” – winter/summer settings:
• “Outdoor temperature” – outdoor temperature is set to calculate the 3-day average (0-20°C); when the outdoor temperature drops below the set
value within three days, the function “OFF permit” is enabled
• “Summer” – the date of the summer season beginning, where “Calendar” is selected
• “Winter” – the date of the winter season beginning, where “Calendar” is selected
Only by “FLEX” remote control (password required)
Menu > Additional> Service > Seasons>Menu configuration>Seasons
• “OFF mode” – unit shut-down option.
• “OFF time” – {24h – 0h} how long the unit can be off based on the selected season:
24h – off time is not limited, the items “OFF season” and “Seasons are not used.
Xh – during the selected season the unit can be switched off only for a period of the selected number of hours per 24 hours.
0h – it cannot be switched off during the selected season.
“OFF Season” – {in summer, winter, always} during which season the function “OFF permit” can be active by means of the unit shut-down function
Where the supply air temperature drops below 16.5°C, the unit control automation records it as the minimum permissible supply air temperature and
the message “critical supply temperature” is shown on the remote control. By activating this function it is possible to choose how long low temperature
may be supplied before the message is shown.
Other information:
Menu > additional > Service>AF>PassiveTC
The duration of low outdoor temperature before the message is shown:
Menu > additional > Service>AF>Excercise
Off – only when the temperature drops to PassiveTC”
Function adjustment, setting:
Only by “FLEX” remote control (password required)
Activation of the minimum supply air temperature (16,5 C) function (by default off”)
„Meniu“ > „Extra“ > “Service” > AF menu PassiveTC OFF/ON
Night ventilation – room cooling by bringing in night-time air. It is normally on, where outdoor temperature in the daytime is >26°C, and in the night-time
it is <16°C. In the night-time room temperature must be >17°C. Every 3 hours the unit switches on for 5 minutes: it measures the supply air and room
temperature. If the room temperature becomes higher than the desired temperature 5 minutes later, and the outdoor temperature is lower than the set
night-time outdoor temperature, the unit is on until the outdoor temperature starts exceeding the set night-time outdoor temperature OR the room is
cooled down to the set temperature. Standard parameters can be changed in the service menu.
Function adjustment, setting:
Only by “FLEX” remote control (password required)
Menu>Additional>Service>NightCtrl.
“Night Control” – night cooling settings. The function will be on, where the outdoor temperature limit set by “day T” is exceeded for the operating unit,
and outdoor temperature drops below
“NightT” and room temperature does not drop below “Room T” after the unit has been switched off.
• “day T” – {15-40}°C maximum outdoor temperature
• “Night T” – {0-15}°C minimum outdoor temperature
• “Room T” – {10-30}°C room temperature
• “Exercise” – {0-5} h. Purging and measuring take place regularly. If the setting is “0”, outdoor sensor must be routed outdoors.