Smarty 3X VE / Smarty 3X VE 3.0
www.salda.lt
Extern. Fan
Supply and extract air fan relay speed activation.
LED8
Pump
-
Not used
-
Outs. Damper
EXT+ ir EXT-
Damper opening
LED2+LED3
Extr. Damper
EXT+
Damper closing
LED3
Preheater
X16-34
Preheater activation.
LED12
Rotor fail
-
Rotor failure imitation (under real conditions where rotor PID is
100%, then rotor error is indicated in 120 s. Where it is lower
than 100%, the time is recalculated, rotor failure is shown on
the remote control.)
Overheat
LOW-COM short circuiter. Remote control shows “V”
Motor overheat
-
Not used
Exchanger
-
Not used
A3 Filter
-
Not used
Extern. Off
Fire input
A1-A1
Fire alarm activation.
Extract humidity
X40
Extract air humidity sensor readings
Supply air temp.
X39
Supply air temperature sensor failure
Extract air temp.
X38
Extract air temperature sensor readings
Outdoor air temp.
Extract air temperature sensor readings
Exhaust air temp.
Outdoor temperature sensor readings
Water temperature
-
Exhaust air temperature sensor readings
Extract CO2
-
Not used
External alarm
CO2 transmitter readings
V2.3 programe coefficients
Program
SMARTY 3XVE-V2.3-2k
Extra
Modbus
MBAddress
1
Parity
None
Baudrate
4800
Stop
1
Vent.Ctrl.
Mode
Supply
Min Supply
..
Max Supply
..
OutDoor T.C.
..
Cool. Ctrl.
Min Supply
6
ºС
DX_CoolOn
23 %
DX_CoolOff
20 %
OutDoor T.C.
12
ºС
Add. Func.
Night Cool.
Off
CO2
..
Fast Butt.
standby
FanStopTime
60s
Boost Ctrl.
Boost timer
0 min
Boost SAF
130 %
Boost EAF
130 %