18

Fault

Probable cause

Recommended solution

Pump will not start

Electrical

Check power supply
Check fuse
Check circuit breaker

Inlet/outlet connections
incorrect

Check that connections are plumbed the correct 
way round and all valves are open

Float sticking in outlet
Flow switch malfunction

Ensure no debris is in outlet area
Contact our technical advisors on 0191 516 2002

Reduced/ 
intermittent flow

Incorrect or no anti-aeration 
flange fitted

Check that installation complies with Salamander 
instructions

Blocked inlet filters

Ensure that all filters and shower head are free  
from debris

Couplers restricting flow

Ensure that all AV couplers are straight and not bent 
or distorted

Air in system

Run system on full hot with pump switched off  
(i.e. gravity only) for several minutes.

Check cold water storage is correct for installation 
and pump is fitted to Salamander instructions.
Ensure cold water refill rate is adequate for 
installation.

Check that vents are fitted as described in 
instructions.

Wrong size pump for system

Ensure pump is sufficient to run the equipment

Hot temp set too high

Reduce cylinder stat setting to 65ºC max or fit HWS/
TMV

Pump starts with all 
outlets closed

Leak in system

Check for leaks

Outlet open

Ensure all outlets are fully closed or capped – i.e. no 
dead legs in pipework

Pump is noisy

Air in system

See previous page

Pump vibrating on surface

Ensure rubber feet are fitted to pump

AV couplers causing vibration Ensure that all AV couplers are straight and not bent 

or distorted

Pump is leaking

Pump exposed to mains 
water pressure

Check that installation complies with Salamander 
instructions

Pump has suffered chemical 
damage

Ensure that the pump has not come into contact 
with chemical substance i.e. solder flux

Pump exposed to excessive 
temperature

Is effective temp control fitted (cylinder stat or HWS/
TMV valve)?

Pump appears to have leaked 
but not sure

Check leak is not from fitting in pipework above 
pump

Pumps above hot 
cylinder becomes 
noisy/low pressure 
during use

Aeration or water starvation

An essex flange may be required for the hot 
connection to cylinder. Ensure pump is a minimum 
of 600mm below the cold water tank.

x203623_salamander_p2_lh.indd   18

14/02/2019   13:04

Summary of Contents for EVE

Page 1: ...1 Pump Installation and Warranty Guide ISSUE A...

Page 2: ...r similarly qualified person in order to avoid a hazard Correct installation is the guarantee of safety and a trouble free system It is therefore important to read these instructions thoroughly and en...

Page 3: ...ow EVE 5 Assembling EVE 7 Pre installation checklist 8 Installation instructions 9 Typical installations 10 Operating instructions 13 Mode selection 14 General specification 15 Trouble shooting 17 Pum...

Page 4: ...urises the system 2 EVE has 3 selectable modes 1 5bar 2 0bar 3 0bar 3 EVE speeds up when more Water is needed The graph shows how EVE s output pressure remains constant as the output flow increases St...

Page 5: ...5 Getting to know EVE 8 7 6 4 5 2 3 1 1 Hot or cold outlet 2 Hot or cold outlet 3 Hot or cold inlet 4 Hot or cold inlet 5 MODE panel 6 Warranty information 7 Rating label 8 X4 Vibration dampening feet...

Page 6: ...iso push fit 9A Isolation valve 9B Pipe release collar 10 X2 Straight 22mm coupler with iso push fit 11 X2 Outlet rubber washers 12 X2 Inlet filter washers 13 ERROR lights 14 Power indicator 15 MODE s...

Page 7: ...7 Assembling EVE 12 8 8 12 11 11 10 10 9 9...

Page 8: ...ght plus one quarter turn The maximum static head should be 10m equivalent to 100kPa 1 0 bar pressure EVE will automatically activate for 3 seconds after 24 hours of inactivity Don ts Never turn on th...

Page 9: ...amage which will invalidate your warranty The hoses are supplied two each angled and straight with each pump This arrangement of couplers facilitates the connection of the supply pipework from any dir...

Page 10: ...ards capacity should be enough for your requirements per bathroom or per shower room or en suite Ball valve should fill on an opposite side of the tank to the pump feed and any other cold services 2 V...

Page 11: ...11 1 5 4 8 9 7 3 6 11 10 2 Figure 1...

Page 12: ...12 4 1 2 5 3 Figure 2...

Page 13: ...linder Before you finish Commissioning First flush inlet pipework and carefully fill pump with water by discharging water from the outlet flexible hose into a container If it is a negative head system...

Page 14: ...your shower loses pressure EVE will speed up to adjust for it All modes can be used in positive head and negative head installation types MODE selection The output pressure of the pump can be varied t...

Page 15: ...fluid temperature 5 C Standards and approvals Splash proof rating IPX2 Complies with the requirements of current British and European safety standards for household and similar electrical appliances...

Page 16: ...bar 3bar Maximum water temperature 65 C Connections Pump connections 3 4 BSP Flexible hoses Connections UK model 3 4 Female x 22mm push fit x 280mm long isolating valves on all hoses Motor Type Brushl...

Page 17: ...ected to reset the lockout Steady Excessive aeration or water starvation has been found Protection has been initiated and the pump has locked out Flash EVE is regulating the motor speed in order to co...

Page 18: ...in instructions Wrong size pump for system Ensure pump is sufficient to run the equipment Hot temp set too high Reduce cylinder stat setting to 65 C max or fit HWS TMV Pump starts with all outlets clo...

Page 19: ...ent Our PumpWise helpline is here to help you and we aim to provide a support service second to none Installers and customers can be sure of a speedy response to requests for technical help guidance a...

Page 20: ...chaser of the equipment from a dealer and not an assignee or subsequent purchaser of the equipment You must evidence the date of purchase by retaining the original invoice from the dealer Without such...

Page 21: ...21 Notes...

Page 22: ...22 Notes...

Page 23: ...23 Notes...

Page 24: ...ue Enterprise Park West Sunderland SR5 3XE Get in touch we re here to help call us on 0191 516 2002 Register your warranty Apply online at www salamanderpumps co uk Apply by phone 0191 516 2002 Unit 2...

Reviews: