Light Commercial R410A on-off
S13-01.01.13en
(5)For the other types indoor unit
0.5Hz
5Hz, Timer lamp on
It cannot recover unless
5Hz
5Hz
lamp flashing at 5Hz
LEDs’ for the indication of outdoor trouble
Note:
1. If the LED1-LED3 are flashing slowly, means the system is stand-by.
2. T3: Outdoor condenser temperature sensor
3. T4: Outdoor ambient temperature sensor
Outdoor Units. Troubleshooting
98
Type
Contents
LED1
LED2
LED3
Trouble
Phase sequence
Flash
Off
Off
Trouble
Lack of phase(A,B)
Flash
Off
Off
Trouble
Lack of phase(C)
Off
Off
Off
Trouble
Protection of Low pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Off
Flash
Trouble
Communication malfunction
Flash
Off
Flash
Trouble
Open-circuit and short-circuit trouble of T3
Off
Flash
Flash
Trouble
Open-circuit and short-circuit trouble of T4
Off
Flash
Off
Trouble
High temperature protection of condenser
Flash
Flash
Flash
No.
Type
Contents
LED Flashing
Remark
1
Normal
Standing-by
Operation lamp flashes at
Nothing wrong with the
unit when LED indicate
these contents.
2
Normal
System Off
All lamps are off
3
Normal
System startup
Operation lamp on
4
Normal
Forced cooling
Operation lamp flashes at
5
Protection
Over current protection of the
compressor occurs 4 times in 1h
Lamps of operation, timer,
defrosting (only fan)
flashing simultaneously at
5Hz.
Whole unit is shut down.
power is cut off
6
Protection
Outdoor protection (lack of
phase, phase sequence and
temperature protection)
All lamps flashing at 5Hz
Recover automatically
after errors are
eliminated (For T3
malfunction of 5HP,
can’t
recover automatically)
7
Error
Room temperature sensor
checking channel is abnormal
Timer lamp flashing at 5Hz
8
Error
Evaporator sensor checking
channel is abnormal
Operation lamp flashing at
9
Error
Condenser sensor checking
channel is abnormal
Defrosting lamp flashing at
10
Error
Communication of EEPROM
malfunction
Operation lamp and timer
11
Error
Water level alarm/pump sensor
malfunction
Alarm lamp flashes at 5Hz
Summary of Contents for SOB-50VA
Page 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013...
Page 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5...
Page 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47...
Page 62: ...Light Commercial R410A on off S13 01 01 13en SIB 50TAV SIB 60TAV Indoor Units Ceiling Floor 61...
Page 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67...
Page 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68...
Page 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90...
Page 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91...
Page 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92...