1.
Specifications
copper tube
piping
heating:-5~24
Notes
: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27
°CDB, 19°CWB; Outdoor temp: 35°CDB;
Nominal heating capacities are based on the following conditions:
Indoor temp: 20
°CDB; Outdoor temp: 7°CDB, 6°CWB;
Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic
room.
2.
3.
Outdoor Units
83
Model
SOB-50VA
SOB-60VA
Power supply
V-ph-Hz
220~240-1-50
220~240-1-50
Max. input consumption
W
2950
3450
Max. input current
A
15
18
Compressor
Model
PA225X2CS-4KU1
PA290X3CS-4MU1
Type
Rotary
Rotary
Brand
GMCC
GMCC
Capacity
Btu/h
18493/18698
24498
Input
W
1855/1940
2430
Rated current(RLA)
A
8.7/8.7
11.4
Locked rotor
Amp(LRA)
A
36.8
61
Thermal protector
Internal
Internal
Capacitor
μF
50
μF/440V-450V
50μF/440V-450V
Refrigerant oil
ml
ESTER OIL VG74 750
ESTER OIL VG74/950
Outdoor fan
motor
Model
YDK48-6H(A)
YDK100-6D
Qty
1
1
Input
W
110
168.7
Capacitor
μF
3
μF/450V
5
μF/450V
Speed
r/min
890
900
Outdoor coil
Number of rows
2
2
Tube pitch(a)
× row
pitch(b)
mm
21x13.37
21x13.37
Fin spacing
mm
1.4
1.4
Fin type
Hydrophilic aluminum
Hydrophilic aluminum
Tube outside dia.and
type
mm
φ7, Inner grooved
copper tube
φ7, Inner grooved
Coil length
× height
× width
mm
658x546x26.74
785x651x26.74
Number of circuits
4
4
Outdoor air flow
m
3
/h
2439
3200
Outdoor noise level (sound pressure)
dB(A)
54
55
Outdoor unit
Dimension(W
×H×D)
mm
762x593x282
845
×695×324
Packing (W
×H×D)
mm
887
×645×355
965
×755×395
Net/Gross weight
kg
39/42
53/57
Refrigerant
Type
R410a
R410a
Charged volume
g
1400
1900
Throttle type
Capillary
Capillary
Design pressure
MPa
4.2/1.5
4.2/1.5
Refrigerant
Liquid side/ Gas side
mm
φ6.4/φ12.7
φ9.5/φ15.9
Max. pipe length
m
25
25
Max. difference in
level
m
15
15
Ambient temp.
℃
cooling:21~43;
heating:-5~24
cooling: 21~43;
Summary of Contents for SOB-50VA
Page 1: ...S13 01 01 13en Light Commercial Air Conditioner R410A ON OFF Service Manual 2013...
Page 6: ...Light Commercial R410A on off S13 01 01 13en 2 2 Outdoor Units General Information 5...
Page 48: ...Light Commercial R410A on off S13 01 01 13en 4 Service Space Indoor Units Ceiling Floor 47...
Page 62: ...Light Commercial R410A on off S13 01 01 13en SIB 50TAV SIB 60TAV Indoor Units Ceiling Floor 61...
Page 68: ...Light Commercial R410A on off S13 01 01 13en 3 Dimensions Indoor Units HSP Duct Type 67...
Page 69: ...Light Commercial R410A on off S13 01 01 13en Indoor Units HSP Duct Type 68...
Page 91: ...Light Commercial R410A on off S13 01 01 13en 5 Wiring Diagrams SOB 50VA Outdoor Units 90...
Page 92: ...Light Commercial R410A on off S13 01 01 13en SOB 60VA SOB 100YA Outdoor Units 91...
Page 93: ...Light Commercial R410A on off S13 01 01 13en SOB 140YA SOB 200YA Outdoor Units 92...