Light Commercial R410A on-off
S13-01.01.13en
d. Outdoor unit malfunction
Outdoor unit malfunction
No
Whether the outdoor unit is power on
Check when the power is on
Yes
No
Replace the outdoor unit
board
Measure whether the voltage of the communication line
’s red and black end
between the indoor and outdoor unit is +5V
Yes
Check the indoor unit main board CN5 or replace the main control board
Yes
Replace indoor PCB
e. EEPROM malfunction
EEPROM malfunction
Yes
EEPROM chip is broken
Replace EEPROM
No
Yes
Replace 9177 chip
Check whether the main control chip 9177 is broken
No
Check PCB board or replace the main control board
Outdoor Units. Troubleshooting
100