BATTERY PANEL
7
TECHNICAL DATA
High voltage alarm
Threshold voltage: Adjustable from 24V to 33V
Factory preset to 29,5V ±2%
Low voltage alarm
Threshold voltage: Adjustable from 20.5V to 24.0V
Factory preset to 23.5V ±2%
AC-alarm
Input type selectable between relay contact or voltage input.
Relay contact:
“No Alarm” ~ open circuit
“Alarm” ~ short circuit
(Open circuit voltage: 1.2V, Short circuit current: 6mA)
Voltage input:
No Alarm” 24V DC nom.
“Alarm” 0V DC
(Input current at 24 V DC: 6mA)
The selection between Relay contact or Voltage input is determined by
jumper setting. See ’Installation’.
Factory preset: Relay contact
Alarm sound mute time
10 min. or infinite is selected by internal jumper setting. See ‘Installation’.
Factory preset: infinite