BATTERY PANEL
Setting of AC alarm 2 input type:
On the figure jumpers S4 and S6 ( pos. 6) are shown in the relay
contact position.
1. To change to the voltage input both S4 and S6 must be set to the
oposite position
2. Apply an input voltage to the X2 terminals ‘AC Alarm V’ and
‘AC Alarm C’.
3. Check that no voltage gives alarm and that the alarm stops when
24V DC is applied.
Setting of single or dual battery:
On the figure jumper S8 ( pos. 7) is shown in dual battery position.
1. To change to single battery the jumper S8 must be set to the oposite
position.
2. Check that the battery shift function is inhibited.
Setting the mute time:
On the figure jumper S5 ( pos. 8) is shown in infinite mute time
position.
1. To change mute time to 10 minuttes the jumper S5 must be set to
the oposite position.
INSTALLATION