ALLEN-BRADLEY PANELVIEW COMPONENT C400
OPERATIONAL GUIDE
Reference 230 – for use with Sahara Model HC Heat-of-Compression – no heater
Rev 2
Page 17 of 17
10/17/2013
K.
Program Steps (continued)
11
480 min.
If the dew point rises above the analyzer setpoint or the Dew Point/
+stdby Timer selector switch is on Timer then;
De-energize SV5-1;
Closes V13
GOTO STEP 1
NOTES:
1.) At any time during the cycle, if Inlet temperature (TT1) drops below the
setpoint (225
F / 107°C) then;
“Low
Regeneration
Temperature” Alarm
2.) At any time during the cycle, if the cooler outlet temperature (TT3) rises
above the setpoint (105
F / 40.56°C) then;
“High Cooler Outlet Temperature” Alarm
3.) At any time during the cycle, if the dew point (DPDS) rises above the
setpoint (-20
F / -29°C) for more than five continuous minutes then;
“High Dew point” Alarm
4.) At any time during the cycle, if the compressor goes unloaded (CR1) then
stop the timing cycle of the dryer until the compressor is loaded.