ALLEN-BRADLEY PANELVIEW COMPONENT C400
OPERATIONAL GUIDE
Reference 230 – for use with Sahara Model HC Heat-of-Compression – no heater
Rev 2
Page 5 of 17
10/17/2013
D.
Status
The STATUS screen will display the dryer’s current cycle status.
The line below the screen name will display which tower is onstream.
The next line is the regeneration cycle in which the opposite tower (regenerating)
is in. This will toggle from HEATING to STRIPPING to REPRESSURIZATION to
COOLING. If the optional Dew Point Demand System (DPDS) is installed, this
will also display STANDBY in the cycle.
The bottom left of the STATUS screen gives the time remaining in the current
regeneration cycle. This starts counting down from 90 minutes for heating, 90
minutes for stripping, and 60 minutes for cooling. Note: When the dryer is in
STANDBY for the optional DPDS, the time remaining will read zero.
A screen selector list is located at the right of the touch screen and is used to
navigate to the other screens. Use the up or down arrow keys to select a screen
name, then press the enter key.