17/45
3.8. Electrical interfaces
3.8.1. Power connection
Power connectors used for Battery and Inverter (-polarity) connections: PV-ADBP4/6 from Multi-
contact.
Figure 7: -polarity power connector
Power connectors used for Battery and Inverter (+polarity) connections: PV-ADSP4/6 from
Multi-contact.
Figure 8: +polarity power connector
3.8.2. Electrical connection
The modules must be connected only after their installation: connect them together and
to the BMM, as shown in the drawing below, with the red power cable delivered with module.
Then, connect the modules together and to the BMM with the three kinds of cables delivered
with the battery (see §2):
Inter-module ribbon cables
Module to BMM ribbon cable
Termination connector ribbon cable
Then, connect inverter to the BMM
“Battery converter” connectors.
Never start the battery system without connecting battery cables and inverter cables to
the BMM.
Never connect a charger with a voltage below the battery voltage.