Opal Pro to Mod TCP
Page 11
Output
Words
(Polled)
AB Ethernet
IP
Name
Description
Bit 0 – Ready to Run (drive is enable
and has 3 phase power)
Bit 1 –Running (start is regulating)
Bit 2 – Full On (starter is phased fully
on)
Bit 3 – Up to Speed (started is
phased fully on and the current is
below 105% of nameplate current as
set in 13.01)
Bit 4 – Reverse
Bit 5 – Jogging
Bit 6 – DC Injecting
Bit 7 – Faulted
Bit 8 – IOC Fault
Bit 9 – MOL Fault
Bit 10 – Phase Loss Fault
Bit 11 – Shear Pin Fault
Bit 12 – Shorted SCR Fault
Bit 13 – Heat Sink OT Fault
Bit 14 – Reserved
Word 1
Input Word 0
Status
Bit 15 – Watch Dog Bit
Word 2
Input Word 1
Current
Feedback
833 = 500% of motor name plate
current as set in 13.01
Word 3
Input Word 2
Phase Angle
Actual
Amount of time phased on in
microseconds
Parameter
AB Ethernet
IP
Name
Description
1.01
Input Word 3
Current
Current feedback in Amps
1.02
Input Word 4
L1 to L2
Voltage
Line 1 to Line 2 Voltage in Volts
1.03
Input Word 5
L1 to L3
Voltage
Line 1 to Line 3 Voltage in Volts
1.04
Input Word 6
L2 to L3
Voltage
Line 2 to Line 3 Voltage in Volts
Digital input status
Bit 0 – Start
Bit 1 – Stop
Bit 2 – Jog
Bit 3 – Reverse
1.05
Input Word 7
DI Status
Bit 4 – Reset
1.06
Input Word 8
Analog Input
Analog input value in Volts X 100