Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
008831 en 2022.02
73/175
Legend (Covers all P&I diagrams in this manual)
C
Compressor
TSH
Temperature switch high alarm
CV
Check valve
TW
Thermowell
DP
Discharge pressure
VI
Vi control
FG
Flow glass
SB-2
Inlet bearing and balance piston
HV
Hand valve
SB-3
Discharge bearings and seal
HTR
Heater
SC-1 Slide valve - unload
LG
Level glass
SC-2 Slide valve - load
LSLL
Separator low oil level shutdown
SC-3 Moveable slide stop
M
Motor
SC-4 Moveable slide stop
1MC
Motor control centre
SC-5 Inlet pressure
2MC
Motor control centre
SC-6 Discharge pressure
NOS
No oil switch
SC-7 Seal weepage
OF
Oil filter
SC-8 Oil drain connection
OP
Oil pressure
SC-9 Inlet housing oil drain
P
Demand pump
SC-
13
Oil drain cylinder
PAH
High discharge pressure alarm
SE-1
Electrical connection
PAHH High discharge pressure shutdown
SE-2
Electrical connection
PAL
Low pressure alarm
SL-1
Liquid injection low Vi
PALL
Low pressure shutdown
SL-2
Liquid injection high Vi
PDAH High pressure differential alarm
SM-1 Main oil injection
PDI
Pressure differential indicator
SV-1
Vapour injection tongue and groove
PDSL-
L
Compressor low diff. pressure cut-out
SD-1 Coalescer bleed str trh O-ring port
TW-1 Thermowell
PE
Pressure transducer
Pressure transducers indicate:
PI
Pressure indicator
PE-1 Oil pressure (manifold)
PIC
Pressure indicator controller
PE-2 Oil pressure before filter
PM
Pump motor
PE-3 Discharge pressure
PS
Pressure switch control
PE-4 Suction pressure
PSV
High pressure safety valve
Temperature probes indicate:
SP
Suction pressure
TE-1 Suction gas temperature
STR
Strainer
TE-2 Discharge gas temperature
TAH
High temperature alarm
TE-3 Lubricating oil temperature
TAHH High temperature shutdown
TE-4 Separator oil temperature
TAL
Low oil temperature alarm
Solenoid valve function:
TALL
Low oil temperature shutdown
YY-1 Energise unload slide valve
TC
Temperature controller
YY-2 Energise increase volume rate
TCV
Thermal control valve
YY-3 Energise increase volume ratio
TE
Temperature element
YY-4 Energise decrease volume ratio
TI
Temperature indicator
YY-5 Solenoid valve
TS
Temperature switch
YY-9 Dual-port liquid injection solenoid
Note:
On units delivered without valves, the bracketed figures near the branches on the P&I di-
agram refer to the component numbers in the list in subsection
These components must be fitted by the customer.