76
English
TAB
ENTER
V1
V2
ENTER
ENTER
89
95
ENTER
ENTER
• SETTING THE FAN AIR
FLOW RATE
From the main menu, access the “
TECH
” menu
and press the “
+
” key to display the "
TAB
” menu.
To activate the required menu, press the central
ENTER key.
Once the unit has been installed and pow-
ered, the air flow rate must be set.
The display will prompt you to set the flow rate of
fan V1 (supply fan);
access the menu by pressing the central enter key;
set the project flow rate (m
3
/h) using the “
+
” or
“
-
” keys.
Press the enter key to confirm.
After confirming, it automatically switches to the air
flow rate setting of fan V2
(extraction fan):
set the project flow rate (m
3
/h) using the “
+
” or
“
-
” keys.
Press the enter key to confirm.
Before carrying out the calibration, the fans are
set to the default flow rate.
ATTENTION: If no flow rate calibration procedure
is carried out, the machine will operate using the
default flow rate as the calibration flow rate for
both fans. The default flow rate corresponds to the
reference value with respect to EU Reg. 1253/14 and
is equal to 91 m3/h.
TECHNICAL MENU
"
TECH
"
The
“
TECH
”
menu must only be used by
the installer or by qualified personnel.
Summary of Contents for Energy SHP-130
Page 29: ...29 Italiano Installazione del comando a muro 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 ...
Page 59: ...59 Italiano ...
Page 85: ...85 English 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Installing controller on the wall ...
Page 115: ...115 English ...
Page 141: ...141 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Français Installation de la commande au mur ...
Page 171: ...171 Français ...
Page 197: ...197 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56 Español Instalación del mando en la pared ...
Page 227: ...227 Español ...