S+S Regeltechnik THERMASGARD ALTM2-Q Operating Instructions, Mounting & Installation Download Page 8

G  

Installation and Commissioning

Devices are to be connected under dead-voltage condition. Devices must 
only be connected to safety extra-low voltage. Consequential  damages 
caused by a fault in this device are excluded from warranty or liability. 
These devices must be installed and commissioned by authorised 

 

specialists. The technical data and connecting conditions shown on the 
device labels and in the mounting and operating instructions delivered 
 together with the device are exclusively valid. Deviations from the  
catalogue representation are not explicitly mentioned and are possible 
in terms of technical progress and continuous improvement of our  
pro ducts. In case of any modifications made by the user, all warranty 
claims are  forfeited. Operating this device close to other devices that 
do not comply with EMC directives may influence functionality. This  
device must not be used for monitoring applications, which serve the 
purpose of protecting persons against hazards or injury, or as an  
EMERGENCY STOP switch for systems or machinery, or for any other 
similar safety-relevant purposes.
Dimensions of housing or housing accessories may show slight 

 

tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original packing 
will be accepted.

Notes on commissioning:

This device was calibrated, adjusted and tested under standardised 
conditions. When operating under deviating conditions, we recommend 
performing an initial manual adjustment on-site during commissioning 
and subsequently at regular intervals.

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and 
standards applicable for the place of measurement (e.g. such as welding 
instructions, etc.). Particularly the following shall be regarded:
–  VDE  ⁄  VDI directive technical temperature measurements, measurement 

set - up for temperature measurements.

–  The EMC directives must be adhered to. 
–  It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with the shielding being 

 attached at one side to the DDC  ⁄  PLC.

Before mounting, make sure that the existing thermometer‘s technical 
parameters comply with the actual conditions at the place of  utilization, 
in particular in respect of:
–  Measuring range 
–  Permissible maximum pressure, flow velocity 
–  Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

CONNECTING CONDITIONS
Output:   0  - 10  V

The output voltage follows linear to the temperature signal applied at  
the input terminals and generates a proportional output signal of 0 - 10 V. 
The voltage outputs are short-circuit proof against ground wire. Applying 
voltage supply to the output terminals will destroy the device.

Output:   4 ... 20 mA

In case of the 4 ... 20 mA measuring transducer, display and evaluating 
 elements are connected in series in the current loop. The measuring 
transducer thereby liWiths the flowing current in variance of the 

 

input signal. 4 mA are for the measuring transducer‘s internal current  
consumption. The apparent ohmic resistance can either be connected in 
the plus or minus path of the measuring transducer. In case of an apparent 
ohmic resistance in the plus path, power supply and resist.

SAFETY REGULATIONS

These devices shall only be used for their intended purpose. Respective 
safety regulations issued by the VDE, the states, their control authorities, 
the TÜV and the local energy supply company must be observed. The 
buyer has to ensure adherence to the building and safety regulations and 
has to avoid all dangers of any kind. We do not assume any warranty for 
faults or damages arising or resulting from improper use of our equipment 
or from non-observance of operating instructions. These instruments 
must be installed by authorised specialists only!

Preferably shielded cables should be used in order to prevent damages  ⁄  
errors. It is imperative to avoid laying parallel with current- 
carrying lines. EMC directives must be adhered to.

G  

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be 

observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the 

TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent 

perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous  

improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation 

by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Summary of Contents for THERMASGARD ALTM2-Q

Page 1: ...nge switching and active output F Notice d instruction Sonde de temp rature d applique pour conduites avec convertisseur y compris collier de serrage talonnable avec commutation multi gamme et sortie...

Page 2: ...5 KL M12x1 5 64 M12x1 5 64 39 49 4 3 72 43 3 14 8 M16x1 5 107 14 8 37 8 M16x1 5 6 15 50 15 M12 Steckverbinder optional auf Anfrage M12 connector optional on request connecteur M12 en option et sur dem...

Page 3: ...1 5 m andere L ngen und Mantelmaterialien z B PTFE oder Glasseide mit Stahlgeflecht optional auf Anfrage Sensorschutz ALTM2 Rohranleger aus Edelstahl V4A 1 4571 6 mm L 50 mm elektrischer Anschluss 0 1...

Page 4: ...UB f r 15 36 V DC Einspeisung und UB bzw GND als Masseleitung zu verwenden Werden mehrere Ger te von einer 24 V AC Spannung versorgt ist darauf zu achten dass alle positiven Betriebsspannungseing nge...

Page 5: ...e und Bedie nungsanleitung Abweichungen zur Katalogdarstellung sind nicht zus tz lich aufgef hrt und im Sinne des technischen Fortschritts und der ste tigen Verbesserung unserer Produkte m glich Bei V...

Page 6: ...materials e g PTFE or glass fibre with steel mesh available on request Sensor protection ALTM2 pipe feeder made of stainless steel V4A 1 4571 6 mm L 50 mm Electrical connection 0 14 1 5 mm via termin...

Page 7: ...utputs of field devices must be referenced to the same potential In case of reversed polarity at one field device a supply voltage short circuit would be caused by that device The consequential short...

Page 8: ...l only be used for their intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The buyer ha...

Page 9: ...t riaux de gaine par ex PTFE ou fibre de verre sous tresse m tallique en option sur demande Protection de capteur ALTM2 Sonde d applique pour conduites en acier inox V4A 1 4571 6 mm L 50 mm Raccordeme...

Page 10: ...nu il faut utiliser l entr e de tension de service UB pour l alimentation en 15 36 V cc et UB ou GND comme c ble de masse Si plusieurs appareils sont aliment s en 24V ca il faut veiller ce que toutes...

Page 11: ...pprovisionnement en nergie locales sont respecter L acheteur doit respecter les dispositions relatives la construction et la s curit et doit viter toutes sortes de risques Les d fauts et dommages r su...

Page 12: ...C 95 III EN 60 730 IP65 EN 60 529 T V S D 713139052 Tyr 1 ALTM2 IP65 EN 60 529 IP68 EN 60 529 CE EN 61326 2014 30 EU 36 x 15 x r THERMASGARD ALTM Rev 2022 V18 THERMASGARD ALTM 2 ALTM 2 Q WG01 Q ALTM...

Page 13: ...sible range 30 70 C c 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND THERMAS...

Page 14: ...r EMV VDE VDI DDC PLC 0 5 g 0 10 0 10 4 20 mA 4 20 4 VDE r ZVEI VDE EMV...

Page 15: ...rreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissances au moment de la publication Elles servent uniquement informer sur nos produits et leurs possibili...

Page 16: ...n side Display connector max min 10K Offset 12 3 1 2 4 5 3 ON Passive sensor Passive sensor UB 24 V AC DC Output 0 10 V UB GND Internal sensor optional Internal passive sensor optional DIP switches Me...

Reviews: