![S+S Regeltechnik HYGRASGARD Modbus-T3 Series Operating Instructions, Mounting & Installation Download Page 12](http://html1.mh-extra.com/html/s-s-regeltechnik/hygrasgard-modbus-t3-series/hygrasgard-modbus-t3-series_operating-instructions-mounting-and-installation_3441839012.webp)
12
G
HYGRASGARD
®
xx - Modbus - T3
| Configuration
READOUT IN THE DISPLAY
By default, the display indicates the following measured values with the corresponding units
cyclically
and consecutively:
temperature
[°C],
relative humidity
[% r.H.] (Resolution: 1/10 °C or 1/10 % r.H.)
The Modbus interface can be used to program an
alternative output variable
instead of the standard display:
dew point
[°C],
mixture ratio
[g ⁄ kg],
absolute humidity
[g ⁄ m
3
],
enthalpy
[kJ ⁄ kg],
relative humidity
[% r.H.],
temperature
[°C]
In this case, the first line indicates the value while the second line indicates the corresponding unit
statically
.
The index in the third line indicates the display type,
e.g. dew point temperature (see the table “Function 06 Write Single Register”).
Reading:
13.8
Unit:
°C
Index:
1
The Modbus interface allows the display screen to be individually configured, both in the 7 segment range and
in the dot-matrix range. This means that messages such as those from the PLC can be displayed.
For the
individual display
, the register 4x0001 (physical display value) must contain the value 10.
The registers 4x0002 to 4x0022 contain information about the characters and segments to be displayed.
The two left-aligned positions are represented by the register 4x0003 (range -9...99). The value 0 switches
off the display of both positions. The display is only active if the register 4x0002 has positive values.
In the
default setting
(register 4x0001 contains the value 0 for the standard display),
even the characters I-Q (registers 4x0014 to 4x0022) are freely programmable in the dot-matrix range.
In this case, the current measured value is automatically displayed in the 7-segment area.
Composition of Segment Pattern (Register 4x0005)
Bit 0 ......
Dot A
Bit 1 ......
Dot B
Bit 2 ......
Dot C
Bit 3 ......
Dot D
Bit 4 ......
Dot DP2
Bit 5 ......
- -
Bit 6 ......
Dot E
Bit 7 ......
Dot DP1
Bit 8 ......
- -
Bit 9 ......
- -
Bit 10 ....
- -
Bit 11 ....
- -
Bit 12 ....
- -
Bit 13 ....
- -
Bit 14 ....
- -
Bit 15 ....
- -
Dot A
Dot B
Dot C
Dot D
Dot E
Dot DP1
Dot DP2
Dot
A B C D E F G H
Matrix I J K L M N O P Q