AERASGARD

®

    FSFTM - CO2 - Modbus 

Rev.  2021 - V12

ATTENTION!   

The minimum CO2

  

concentration of outdoor air amounts to approx. 350  ppm (output voltage = 1.75 V

 

at  MR = 0...2000  ppm  or  0.7 V  at 

MR = 0...5000  ppm)  in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion.

 

Depending on the changes  

to the concentration and the flow velocity of the air surrounding the  sensor, the reaction of the device to the change of concentration may take  
place with a delay. It is essential to choose an installation location for the device

 

in which the air stream flows around the sensor. Otherwise the gas 

exchange may be  considerably delayed or prevented.   

Commissioning

After the device is switched on, a self-test and temperature equalisation are performed. Depending on the ambient conditions, this process takes 
30-50 minutes (

as an option,

 

manual calibration

 can now be performed). If commissioning with 

automatic calibration

, proceed as follows:

1.

 Open all windows or set the air conditioning system to use outdoor air

2.

 Switch on the device and move away from the device. If possible, all persons should leave the room.

3.

 The device is ready to use after 50 minutes. . 

Automatic calibration of the CO2 measurement – ABC logic

The regular exchange of fresh air is all that is required for the self-calibration technology in the sensor (CO2 concentrations: 350-500 ppm). The 
device detects this condition and performs the calibration automatically. It is sufficient to open the windows or set the air conditioning system to use 
outdoor air at regular intervals and to stop all CO2-producing processes that influence the ambient air. Proceed as follows:

Open all windows fully or set the air conditioning system to use outdoor air 1x weekly for 15-20 minutes.  
If possible, all persons should leave the room during this time.
Regular ventilation of the rooms and flushing of the duct with fresh air will increase the measuring accuracy of the sensor. 

Automatic calibration

 is deactivated by default in the as-delivered condition and, if required, must be activated using the Modbus.

Manual calibration of CO2 measurement

Manual calibration can be carried out irrespective of the ABC logic.  Sufficient fresh air must be provided before and during the calibration procedure 
(CO2 concentration: 350-500 ppm). Also make sure that no CO2-producing processes influence the ambient air. Proceed as follows to perform 
manual calibration:

1.

  Preparation: Remove the housing cover and open all windows or set the air conditioning system to use outdoor air.

2.

  Press and hold the “

ZERO CO2

” button until the flashing LED row changes to a steady light after 5 seconds.  

Devices with a display indicate “

AUTO 0

” and change the countdown from 5 to 600.  

The calibration process has started. Keep the windows open or the air conditioning system set to use outdoor air.

3.

  If possible, all persons should now leave the room.

4.

  After 10 minutes, the calibration is complete (status LED has gone out, the countdown is complete) and the device should indicate or transmit 

a CO2 concentration of between 350-500 ppm.

5

5

6

7

6

7

4

3

4

3

free

free

Shielding

Modbus A

Modbus B

UB– 

GND

UB+ 

24V

AC/DC

Connecting diagram 

FSFTM - CO2 - Modbus

address

Top

1 2 3 4 5 6 7 8

ON

mode

1 2 3 4 5 6

ON

ZERO

Schematic diagram 

FSFTM - CO2 - Modbus

Summary of Contents for AERASGARD FSFTM-CO2-Modbus Series

Page 1: ...sor or measuring transducer in wall in the panel switch programme with Modbus connection F Notice d instruction Sonde d ambiance d humidit de temp rature et de CO2 resp convertisseur de mesure montage...

Page 2: ...RD FSFTM CO2 Modbus D G F r Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dimensional drawing Plan cot 15 5 55 3 43 80 55 80 50 60 60 12 40 5 55 3 80 55 80 50 60 60 FSFTM CO2 Modbus P FSFTM C...

Page 3: ...er keine Sollwertverstellung m glich KOHLENDIOXID CO2 Sensor CO2 optischer NDIR Sensor nicht dispersive Infrarot Technologie mit manueller Kalibrierung ber Zero Taster mit automatischer Kalibrierung a...

Page 4: ...Vorg nge die die Umgebungsluft beeinflussen zu unterbinden Gehen Sie wie folgt vor 1x w chentlich f r 15 20 Minuten alle Fenster komplett ffnen bzw die L ftungsanlage auf Au enluft einstellen Wenn m g...

Page 5: ...ngsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe Tabelle Die Parity wird ber Pos 3 des DIP Schalters B eingestellt Ei...

Page 6: ...fset CO2 Signed 16 Bit 512 511 Offset 4x0022 nicht belegt Signed 16 Bit 512 511 Offset 4x0023 Offset Temperatur Signed 16 Bit 512 511 Offset 4x0024 Offset relative Feuchte Signed 16 Bit 512 511 Offset...

Page 7: ...etrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgeflech...

Page 8: ...achten und Gef hrdungen aller Art zu vermeiden F r M ngel und Sch den die durch unsachgem e Verwendung unserer Ger te entstehen bernehmen wir keine Gew hrleistung Die Installa tion der Ger te darf nu...

Page 9: ...an diesem Ger t entstehen sind von der Gew hrleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Dat...

Page 10: ...h Jaeger CARBON DIOXIDE CO2 Sensor CO2 optical NDIR sensor non dispersive infra red technology with manual calibration via zero button with automatic calibration can be deactivated via Modbus Long ter...

Page 11: ...r at regular intervals and to stop all CO2 producing processes that influence the ambient air Proceed as follows Open all windows fully or set the air conditioning system to use outdoor air 1x weekly...

Page 12: ...efault OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch...

Page 13: ...Signed 16 Bit 512 511 Offset 4x0022 not assigned Signed 16 Bit 512 511 Offset 4x0023 Offset temperature Signed 16 Bit 512 511 Offset 4x0024 Offset relative humidity Signed 16 Bit 512 511 Offset only...

Page 14: ...scribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply...

Page 15: ...ir intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The buyer has to ensure adherence...

Page 16: ...device Consequential damages caused by a fault in this device are excluded from warranty or liability These devices must be installed and commissioned by authorised specialists The technical data and...

Page 17: ...ainsi que valeur de consigne du potentiom tre chez Busch Jaeger aucun r glage de la valeur de consigne possible DIOXYDE DE CARBONE CO2 Capteur CO2 capteur optique NDIR technologie infrarouge non disp...

Page 18: ...r le syst me de ventilation sur air ext rieur tout en vitant toute op ration g n rant du CO2 qui pourrait influencer l air ambiant Proc der comme suit 1 fois par semaine ouvrir compl tement toutes les...

Page 19: ...B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B On peut r gler EVEN paire ou ODD impaire voir tableau La protection par parit...

Page 20: ...Offset 4x0023 Offset temp rature Signed 16 Bit 512 511 Offset 4x0024 Offset humidit relative Signed 16 Bit 512 511 Offset uniquement pour version d appareil avec potentiom tre de consigne Function 08...

Page 21: ...doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alimen...

Page 22: ...age pr vu Les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie locales sont respecter L acheteur doit re...

Page 23: ...ons toute responsabilit ou garantie pour les d fauts et dommages r sultant d une utilisation inappropri e de cet appareil Nous d clinons toute responsabilit ou garantie au titre de tout dommage cons c...

Page 24: ...bus 2 15 CO2 0 5000 1 CO2 30 1 3 CO2 5 1 C 0 5 C 0 13 1 2 1 0 100 0 95 3 0 20 80 25 C 5 0 0 50 C 0 8 K 25 C 55 0 14 1 5 35 85 C 0 50 C 90 III EN 60730 IP20 EN 60529 EN 61326 2014 30 EC GIRA System 55...

Page 25: ...1 30 50 1 2 3 50 CO2 ABC 350 500 1 15 20 Modbus CO2 ABC 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1 5 5 6 7 6 7 4 3 4 3 free free Shielding Modbus A Modbus B UB GND UB 24V AC DC FSFTM CO2...

Page 26: ...28 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON OFF 1 2...

Page 27: ...100 0 3x0009 3x0010 3x0011 16 0 1000 0 0 100 0 05 Write Single Coil 0x0001 Autozero CO2 0 0 1 OFF ON 0x0003 Automatic CO2 2 0 1 OFF ON 06 Write Single Register 16 Write Multiple Register 4x0021 CO2 1...

Page 28: ...odbus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D GND B D0 D MODBUS RTU Master Slave 1 Slave 2 5 B RBIAS RBIAS RAB RAB r AERASGARD FSFTM CO2 Modbus Re...

Page 29: ...29 r VDE...

Page 30: ...30 0 100 0 10 10 0 99 9 0 10 24 CO2 ZVEI VDE EMV VDE VDI 0 5 g r...

Page 31: ...ust be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our General Terms and Conditions Sou...

Page 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Reviews: