S+S Regeltechnik ACO2-W-LCD-TYR2 Operating Instructions, Mounting & Installation Download Page 15

15

G  

Mounting and Installation

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier on AC  supply voltage. 

The output signal is to be tapped by a measuring instrument. The output 
signal is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Putting in operation 

After switching on the device, a self-test and tempering period follows. This procedure takes 30  -  50 
minutes,depending on the ambient conditions. During this time the output analogue voltage differs from the 
actual measured value.

Switching point setting 

A potential-free changeover contact is available as a switch output.  
A switching point between 10 % and 95 % of the measuring range can be selected using  
the SET potentiometer. The 10 % value is added to the fresh air limit of 400  ppm for CO

2

(600...1900  ppm with MR = 0...2000  ppm  or  900...4700  ppm with MR = 0...5000  ppm).
With other measurands, the corresponding lower limit is used directly as a basis.   
(VOC: 10...95 %, Temperature: –23...+74 °C, 

Humidity: 10...95% r.H.)

The assignment of the switch output to measurand is done via DIP switch (DIP 7 and DIP 8).

Offset 

Each measuring channel has a separate offset potentiometer for subsequent adjustment of the measure-
ment. The adjusting range is ± 10 % of the measuring range.

Display 

In the first and second lines, the 

measurements

 with the corresponding 

units 

  

( CO

2

 in 

ppm

, VOC in 

%

, temperature in 

°C

, relative humidity in 

%  r.H.

)  

are displayed in a cyclical series.

In the third line, the 

switching status of the relay

 is shown on the left as a circuit 

(full 

● 

= relay energised;  empty 

 = relay de-energised)  

followed by the corresponding 

indicator 

(

C

 for  CO

2

;  

V

 for VOC;  

T

 for temperature;  

H

 for relative humidity in 

%  r.H.

)  

and the 

switchpoint value

 is shown on the right.

Summary of Contents for ACO2-W-LCD-TYR2

Page 1: ...haltendem Ausgang G Operating Instructions Mounting Installation Multifunctional on wall sensors and measuring transducers for humidity temperature air quality VOC and CO2 content calibratable with ac...

Page 2: ...4 M16x1 5 16 134 AERASGARD AFTM LQ CO2 W ATM CO2 SD AFTM CO2 W AFTM LQ CO2 W ATM CO2 SD SF K Kunststoff Sinterfilter Standard plastic sinter filter standard Filtre fritt en mati re synth tique standa...

Page 3: ...g 24 V AC DC 10 Leistungsaufnahme 4 8 W 24 V DC typisch 6 8 VA 24 V AC typisch Peakstrom 200 mA Ausg nge Axx SD 0 10 V fest eingestellt Axx W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar gew...

Page 4: ...w hlte Variante gilt einheitlich f r alle Ausg nge In der Standard Ausf hrung Axx SD ist 0 10 V fest eingestellt Ausstattung W mit Wechsler Standard Ausf hrung Axx SD ohne Wechsler Hinweis Dieses Ger...

Page 5: ...P 6 deaktiviert OFF aktiviert default ON Relais Zuordnung DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF VOC 10 95 ON OFF Temperatur 23 74 C OFF ON Feuchtigkeit 10 95 r H ON ON Ausgang DIP...

Page 6: ...t belegt Schaltbild ACO2 SD DIP Schalter ACO2 SD CO2 Gehalt DIP1 0 2000 ppm default OFF 0 5000 ppm ON Zero 1 2 3 1 ON DIP CO Ausgang CO 0 10V UB GND UB 24V AC DC 1 2 3 4 ON DIP SET Zero OFFSET 13 11 1...

Page 7: ...hrend des Kalibriervorganges ist f r ausreichend Frischluft zu sorgen Wir empfehlen eine Frischluftzufuhr von mindestens zwei Stunden bevor der Kalibriervorgang gestartet wird Der Kalibriervorgang wir...

Page 8: ...0V GND Versorgung mit AC 24V 0V DC 15 36V GND AC 24V 0V DC 15 36V GND Schaltung 0 10V 0V GND V Versorgung mit Inbetriebnahme Nach dem Einschalten des Ger tes erfolgen ein Selbsttest und die Temperieru...

Page 9: ...im spannungslosen Zustand erfolgen Um Sch den und Fehler am Ger t z B durch Spannungsinduktion zu verhindern sind abgeschirmte Leitungen zu verwenden eine Parallelverlegung zu stromf hrenden Leitunge...

Page 10: ...ures selectively and cannot detect any VOC a VOC mixed gas sensor cannot recognize CO2 molecules TECHNICAL DATA Voltage supply 24 V AC DC 10 Power consumption 4 8 W 24 V DC typical 6 8 VA 24 V AC typi...

Page 11: ...sensor for humidity temperature and CO2 content Deluxe AERASGARD AFTM LQ CO2 W Multifunctional on wall sensor for humidity temperature CO2 content and air quality VOC Deluxe Type WG02 Measuring Range...

Page 12: ...ted OFF activated default ON Relay assignment DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF VOC 10 95 ON OFF Temperature 23 74 C OFF ON Humidity 10 95 r H ON ON Output DIP 9 Voltage 0 10 V...

Page 13: ...ram ACO2 W KCO2 W without display DIP switch ACO2 W CO2 content DIP1 0 2000 ppm default OFF 0 5000 ppm ON CO2 automatic zero point DIP 3 deactivated OFF activated default ON Output DIP 4 Voltage 0 10...

Page 14: ...ently of the DIP switch position Sufficient fresh air must be provided before and after the calibration procedure We recommend a fresh air supply of at least two hours before the calibration process T...

Page 15: ...gh this field device may cause damage to it Therefore pay attention to correct wiring Putting in operation After switching on the device a self test and tempering period follows This procedure takes 3...

Page 16: ...es must only be connected to safety extra low voltage and under dead voltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel wi...

Page 17: ...esure de mani re s lective il ne peut pas d tecter les COV et un capteur de m lange de gaz COV ne peut pas mesurer les mol cules de CO2 CARACT RISTIQUES TECHNIQUES Alimentation en tension 24 V ca cc 1...

Page 18: ...e via interrupteur DIP la variante s lectionn e s applique toutes les sorties Dans le mod le Standard Axx SD 0 10 V est r glage fixe quipement W avec inverseur Mod le Standard Axx SD sans inverseur At...

Page 19: ...FF activ default ON Affectation relais DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF COV 10 95 ON OFF Temp rature 23 74 C OFF ON Humidit 10 95 h r ON ON Sortie DIP 9 Tension 0 10 V default...

Page 20: ...t ACO2 W KCO2 W sans cran Interrupteur DIP ACO2 W Teneur en CO2 DIP1 0 2000 ppm default OFF 0 5000 ppm ON Point z ro automatique CO2 DIP 3 d sactiv OFF activ default ON sortie DIP 4 Tension 0 10 V def...

Page 21: ...air L talonnage manuel peut tre effectu ind pendamment de la position de l interrupteur DIP Avant et pendant le processus d talonnage assurer une alimentation en air frais suffisante Nous recommandons...

Page 22: ...ry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND Mise en service Apr s la mise en marche de l appareil celui ci effectue un autocontr le et l quilibrage de temp rature En fonction des conditions...

Page 23: ...l que sur un r seau de tr s basse tension de s curit Pour viter des endommagements erreurs sur l appareil par ex dus une induction de tension parasite il est conseill d utiliser des c bles blind s ne...

Page 24: ...2 2 VOC NDIR 2 VOC 2 24 10 4 8 24 6 8 24 200 A Axx SD 0 10 Axx W 0 10 4 20 800 DIP 10 Axx SD Axx W 24 1 A DIP 16 L 35 16 L 32 0 100 0 95 2 0 20 80 25 C 3 0 0 10 4 20 A DIP 35 80 C 10 60 C 0 2 K 25 C A...

Page 25: ...LAY 0 2000 5000 1 0 100 W 1501 7111 7371 200 AFTM CO2 W AFTM CO2 W 0 100 35 80 C 0 2000 5000 1 W 1501 7116 7301 200 AFTM CO2 W DISPLAY 0 100 35 80 C 0 2000 5000 1 W 1501 7116 7371 200 AFTM LQ CO2 W AF...

Page 26: ...DIP 7 DIP 8 CO2 600 1900 900 4700 1 OFF OFF VOC 10 95 ON OFF 23 74 C OFF ON 10 95 ON ON DIP 9 0 10 OFF 4 20 A ON DIP 5 4 5 6 12 11 13 OFFSET CO VOC r H C 1 2 3 1 2 3 4 5 6 7 8 9 ON DIP ON ON VOC CO Mo...

Page 27: ...ut temperature in C free r AERASGARD ACO2 W ACO2 SD Rev 2018 V22 ACO2 W KCO2 W DIP ACO2 W DIP1 0 2000 1 OFF 0 5000 1 ON CO2 DIP 3 OFF ON DIP 4 0 10 OFF 4 20 ON DIP2 ACO2 SD DIP ACO2 SD DIP1 0 2000 1 O...

Page 28: ...28 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 ABC automatic background logic CO2 350 400 1 7 24 CO2 400 1 4 21 24 DIP CO2 500 1 Reset CO2 AUTO 0 600 CAL 0 4 1 DIP Reset VOC AUTO 0 200 CAL 0 0 10...

Page 29: ...0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND 30 50 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 VOC 10 95 23 74 C...

Page 30: ...30 r 0 10 4 20 10 95 35 80 C 24 ZVEI VDE EMV...

Page 31: ...C UA V IA mA 35 0 0 4 0 30 0 4 4 7 25 0 9 5 4 20 1 3 6 1 15 1 7 6 8 10 2 2 7 5 5 2 6 8 2 0 3 0 8 9 5 3 5 9 6 10 3 9 10 3 15 4 3 11 0 20 4 8 11 7 25 5 2 12 3 30 5 7 13 0 35 6 1 13 7 40 6 5 14 4 45 7 0...

Page 32: ...onal drawing Plan cot ACO2 W ALQ CO2 W ACO2 SD AERASGARD ACO2 W ALQ CO2 W ACO2 SD ACO2 W ALQ CO2 W mit Display with display avec cran c ACO2 W ALQ CO2 W ACO2 SD ohne Display without display sans cran...

Reviews: