Herzlichen Glückwunsch!  
Sie haben ein deutsches Qualitätsprodukt erworben.
Congratulations!  
You have bought a German quality product.
Félicitations !    
Vous avez fait l’acquisition d’un produit allemand de qualité.
Примите наши поздравления !   
Вы приобрели качественный продукт, изготовленный в Германии.

D

  

Bedienungs- und Montageanleitung

Multifunktionaler Aufputzfühler bzw. Messumformer  
für Feuchte, Temperatur,  
Luftgüte (VOC) und CO

2

 - Gehalt,   

kalibrierfähig, mit aktivem ⁄ schaltendem Ausgang

G

  

Operating Instructions, Mounting & Installation

Multifunctional on-wall sensors and measuring transducers  
for humidity, temperature,  
air quality (VOC) and CO

2

 content,  

calibratable, with active ⁄ switching output

F

  

Notice d’instruction

Sonde (transmetteur) pour montage en saillie  
multifonctionnelle, pour l'humidité, la température,  
la qualité d'air (COV) et de teneur en CO

2

,  

étalonnable, avec sortie active ⁄ tout ou rien

r

  

Руководство по монтажу и обслуживанию

Мультифункциональный датчик для открытой установки ⁄  
измерительный преобразователь,  
для измерения влажности, температуры,  
качества воздуха (VOC) и содержания CO

2

,  

калибруемый, с активным ⁄ релейным выходом

AFTM - CO

2

 - W

 

AFTM - LQ - CO

2

 - W

ATM - CO

2

 - SD 

6000-3450-0000-1XX   

34500-2018  V102

    04  ⁄  2018

S+S REGELTECHNIK GMBH 
PIRNAER STRASSE 20 
90411 NÜRNBERG ⁄ GERMANY

FON  +49 (0) 911 ⁄ 5 19  47- 0 
FAX  +49 (0) 911 ⁄ 5 19  47- 70

[email protected] 
www.SplusS.de

Summary of Contents for ACO2-W-LCD-TYR2

Page 1: ...haltendem Ausgang G Operating Instructions Mounting Installation Multifunctional on wall sensors and measuring transducers for humidity temperature air quality VOC and CO2 content calibratable with ac...

Page 2: ...4 M16x1 5 16 134 AERASGARD AFTM LQ CO2 W ATM CO2 SD AFTM CO2 W AFTM LQ CO2 W ATM CO2 SD SF K Kunststoff Sinterfilter Standard plastic sinter filter standard Filtre fritt en mati re synth tique standa...

Page 3: ...g 24 V AC DC 10 Leistungsaufnahme 4 8 W 24 V DC typisch 6 8 VA 24 V AC typisch Peakstrom 200 mA Ausg nge Axx SD 0 10 V fest eingestellt Axx W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar gew...

Page 4: ...w hlte Variante gilt einheitlich f r alle Ausg nge In der Standard Ausf hrung Axx SD ist 0 10 V fest eingestellt Ausstattung W mit Wechsler Standard Ausf hrung Axx SD ohne Wechsler Hinweis Dieses Ger...

Page 5: ...P 6 deaktiviert OFF aktiviert default ON Relais Zuordnung DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF VOC 10 95 ON OFF Temperatur 23 74 C OFF ON Feuchtigkeit 10 95 r H ON ON Ausgang DIP...

Page 6: ...t belegt Schaltbild ACO2 SD DIP Schalter ACO2 SD CO2 Gehalt DIP1 0 2000 ppm default OFF 0 5000 ppm ON Zero 1 2 3 1 ON DIP CO Ausgang CO 0 10V UB GND UB 24V AC DC 1 2 3 4 ON DIP SET Zero OFFSET 13 11 1...

Page 7: ...hrend des Kalibriervorganges ist f r ausreichend Frischluft zu sorgen Wir empfehlen eine Frischluftzufuhr von mindestens zwei Stunden bevor der Kalibriervorgang gestartet wird Der Kalibriervorgang wir...

Page 8: ...0V GND Versorgung mit AC 24V 0V DC 15 36V GND AC 24V 0V DC 15 36V GND Schaltung 0 10V 0V GND V Versorgung mit Inbetriebnahme Nach dem Einschalten des Ger tes erfolgen ein Selbsttest und die Temperieru...

Page 9: ...im spannungslosen Zustand erfolgen Um Sch den und Fehler am Ger t z B durch Spannungsinduktion zu verhindern sind abgeschirmte Leitungen zu verwenden eine Parallelverlegung zu stromf hrenden Leitunge...

Page 10: ...ures selectively and cannot detect any VOC a VOC mixed gas sensor cannot recognize CO2 molecules TECHNICAL DATA Voltage supply 24 V AC DC 10 Power consumption 4 8 W 24 V DC typical 6 8 VA 24 V AC typi...

Page 11: ...sensor for humidity temperature and CO2 content Deluxe AERASGARD AFTM LQ CO2 W Multifunctional on wall sensor for humidity temperature CO2 content and air quality VOC Deluxe Type WG02 Measuring Range...

Page 12: ...ted OFF activated default ON Relay assignment DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF VOC 10 95 ON OFF Temperature 23 74 C OFF ON Humidity 10 95 r H ON ON Output DIP 9 Voltage 0 10 V...

Page 13: ...ram ACO2 W KCO2 W without display DIP switch ACO2 W CO2 content DIP1 0 2000 ppm default OFF 0 5000 ppm ON CO2 automatic zero point DIP 3 deactivated OFF activated default ON Output DIP 4 Voltage 0 10...

Page 14: ...ently of the DIP switch position Sufficient fresh air must be provided before and after the calibration procedure We recommend a fresh air supply of at least two hours before the calibration process T...

Page 15: ...gh this field device may cause damage to it Therefore pay attention to correct wiring Putting in operation After switching on the device a self test and tempering period follows This procedure takes 3...

Page 16: ...es must only be connected to safety extra low voltage and under dead voltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel wi...

Page 17: ...esure de mani re s lective il ne peut pas d tecter les COV et un capteur de m lange de gaz COV ne peut pas mesurer les mol cules de CO2 CARACT RISTIQUES TECHNIQUES Alimentation en tension 24 V ca cc 1...

Page 18: ...e via interrupteur DIP la variante s lectionn e s applique toutes les sorties Dans le mod le Standard Axx SD 0 10 V est r glage fixe quipement W avec inverseur Mod le Standard Axx SD sans inverseur At...

Page 19: ...FF activ default ON Affectation relais DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700 ppm OFF OFF COV 10 95 ON OFF Temp rature 23 74 C OFF ON Humidit 10 95 h r ON ON Sortie DIP 9 Tension 0 10 V default...

Page 20: ...t ACO2 W KCO2 W sans cran Interrupteur DIP ACO2 W Teneur en CO2 DIP1 0 2000 ppm default OFF 0 5000 ppm ON Point z ro automatique CO2 DIP 3 d sactiv OFF activ default ON sortie DIP 4 Tension 0 10 V def...

Page 21: ...air L talonnage manuel peut tre effectu ind pendamment de la position de l interrupteur DIP Avant et pendant le processus d talonnage assurer une alimentation en air frais suffisante Nous recommandons...

Page 22: ...ry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND Mise en service Apr s la mise en marche de l appareil celui ci effectue un autocontr le et l quilibrage de temp rature En fonction des conditions...

Page 23: ...l que sur un r seau de tr s basse tension de s curit Pour viter des endommagements erreurs sur l appareil par ex dus une induction de tension parasite il est conseill d utiliser des c bles blind s ne...

Page 24: ...2 2 VOC NDIR 2 VOC 2 24 10 4 8 24 6 8 24 200 A Axx SD 0 10 Axx W 0 10 4 20 800 DIP 10 Axx SD Axx W 24 1 A DIP 16 L 35 16 L 32 0 100 0 95 2 0 20 80 25 C 3 0 0 10 4 20 A DIP 35 80 C 10 60 C 0 2 K 25 C A...

Page 25: ...LAY 0 2000 5000 1 0 100 W 1501 7111 7371 200 AFTM CO2 W AFTM CO2 W 0 100 35 80 C 0 2000 5000 1 W 1501 7116 7301 200 AFTM CO2 W DISPLAY 0 100 35 80 C 0 2000 5000 1 W 1501 7116 7371 200 AFTM LQ CO2 W AF...

Page 26: ...DIP 7 DIP 8 CO2 600 1900 900 4700 1 OFF OFF VOC 10 95 ON OFF 23 74 C OFF ON 10 95 ON ON DIP 9 0 10 OFF 4 20 A ON DIP 5 4 5 6 12 11 13 OFFSET CO VOC r H C 1 2 3 1 2 3 4 5 6 7 8 9 ON DIP ON ON VOC CO Mo...

Page 27: ...ut temperature in C free r AERASGARD ACO2 W ACO2 SD Rev 2018 V22 ACO2 W KCO2 W DIP ACO2 W DIP1 0 2000 1 OFF 0 5000 1 ON CO2 DIP 3 OFF ON DIP 4 0 10 OFF 4 20 ON DIP2 ACO2 SD DIP ACO2 SD DIP1 0 2000 1 O...

Page 28: ...28 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 ABC automatic background logic CO2 350 400 1 7 24 CO2 400 1 4 21 24 DIP CO2 500 1 Reset CO2 AUTO 0 600 CAL 0 4 1 DIP Reset VOC AUTO 0 200 CAL 0 0 10...

Page 29: ...0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND 30 50 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 VOC 10 95 23 74 C...

Page 30: ...30 r 0 10 4 20 10 95 35 80 C 24 ZVEI VDE EMV...

Page 31: ...C UA V IA mA 35 0 0 4 0 30 0 4 4 7 25 0 9 5 4 20 1 3 6 1 15 1 7 6 8 10 2 2 7 5 5 2 6 8 2 0 3 0 8 9 5 3 5 9 6 10 3 9 10 3 15 4 3 11 0 20 4 8 11 7 25 5 2 12 3 30 5 7 13 0 35 6 1 13 7 40 6 5 14 4 45 7 0...

Page 32: ...onal drawing Plan cot ACO2 W ALQ CO2 W ACO2 SD AERASGARD ACO2 W ALQ CO2 W ACO2 SD ACO2 W ALQ CO2 W mit Display with display avec cran c ACO2 W ALQ CO2 W ACO2 SD ohne Display without display sans cran...

Reviews: